2-4
E.
F.
G.
Figure 2-4. Menu Progression from the Login Accepted Menu to the
Fire, Supervisory, Trouble Menu
5. Press <Enter> to accept the passcode. (Logging in at Level 4 causes a
Simplex Service Mode Trouble. Acknowledge the trouble and continue.)
The display in (E) appears briefly and then (F) appears after the Simplex
Service Mode trouble is acknowledged.
6. Press <Menu> to start Programming (G).
Follow Steps 1 and 2 to log out of the 4005.
1. Press <Next> to scroll through the menus until [
3DVVFRGH
] is displayed
and then press <Enter>.
2. Press <Next> until [
/RJ2XW
] is displayed and then press Enter.
The 4005 defaults to Level 1 access.
Basic Things to Know About Programming a 4005,
Continued
Default Passcodes
(Continued)
Logout
/RJLQLV$FFHSWHG
&XUUHQW$FFHVV/HYHO
/HYHO
6LPSOH[6HUYLFH0RGH
7URXEOH3RLQW
7URXEOH
),5(
683(59,625< 7528%/(
0HQX >9LHZ3RLQWV@