5-6
Pt. TYPE:
DUCT
Description:
Duct Detector
Circuit Status
LCD Readout (2
nd
line)
LED
Normal Duct
Detector
NORMAL
Limited Duct
Detector
ALARM
A
Open Duct
Detector
TROUBLE
T
Short Duct
Detector
ALARM
A
Disable TBL
Duct Detector
TROUBLE
T
Class A TBL
Duct Detector
TROUBLE
T
Detailed Description:
Used when only Duct Detectors are connected to the
circuit.
Figure 5-15. DUCT Point Type
Pt. TYPE:
FLAME
Description:
Flame Detector
Circuit Status
LCD Readout (2
nd
line)
LED
Normal Flame
Detector
NORMAL
Limited Flame
Detector
ALARM
A
Open Flame
Detector
TROUBLE
T
Short Flame
Detector
ALARM
A
Disable TBL
Flame Detector
TROUBLE
T
Class A TBL
Flame Detector
TROUBLE
T
Detailed Description:
Used when only Flame Detectors are connected to the
circuit.
Figure 5-16. FLAME Point Type
Pt. TYPE:
PULL
Description:
Pull (manual) Station
Circuit Status
LCD Readout (2
nd
line)
LED
Normal
Manual Pull Station
NORMAL
Limited
Manual Pull Station
ALARM
A
Open
Manual Pull Station
TROUBLE
T
Short
Manual Pull Station
ALARM
A
Disable TBL
Manual Pull Station
TROUBLE
T
Class A TBL
Manual Pull Station
TROUBLE
T
Detailed Description:
Used when only Pull Stations are connected to the circuit.
Figure 5-17. PULL Point Type
Continued on next page
Point Type Messages for Monitor Points,
Continued
Monitor Points
(continued)
Technical Manuals Online! - http://www.tech-man.com
Содержание LifeAlarm 4005 Series
Страница 2: ...this is blank text Technical Manuals Online http www tech man com ...
Страница 6: ...this is blank text Technical Manuals Online http www tech man com ...
Страница 58: ...this is blank text Technical Manuals Online http www tech man com ...
Страница 80: ...this is blank text Technical Manuals Online http www tech man com ...
Страница 129: ...6 9 SMPL Programming Continued SMPL Equations continued Technical Manuals Online http www tech man com ...
Страница 141: ...Technical Manuals Online http www tech man com ...
Страница 142: ...This Page intentionally left blank Technical Manuals Online http www tech man com ...