![Simplex LifeAlarm 4005 Series Скачать руководство пользователя страница 103](http://html1.mh-extra.com/html/simplex/lifealarm-4005-series/lifealarm-4005-series_programming-instructions-manual_1276528103.webp)
5-9
Pt. TYPE:
S2STAGE
Description:
2 Stage Monitor
Circuit Status
LCD Readout (2
nd
line)
LED
Normal
2 Stage Monitor
NORMAL
Limited
2 Stage Monitor
ALARM
A
Open
2 Stage Monitor
TROUBLE
T
Short
2 Stage Monitor
ALARM
A
Disable TBL
2 Stage Monitor
TROUBLE
T
Class A TBL
2 Stage Monitor
TROUBLE
T
Detailed Description:
Used for 2 Stage Alarms. The current limited operation
of any device will indicate a STAGE 1 ALARM (press the <
ö
> key to
display). The shorting of the circuit, such as a key switch operation, will cause
a STAGE 2 ALARM (press the <
ö
> key to display).
Figure 5-24. S2STAGE Point Type
Pt. TYPE:
SO
Description:
Sprinkler Supv (normally open)
Circuit Status
LCD Readout (2
nd
line)
LED
Normal Sprinkler
Monitor
NORMAL
Limited Sprinkler
Monitor SUPERVISORY
S
Open Sprinkler
Monitor
TROUBLE
T
Short Sprinkler
Monitor SUPERVISORY
S
Disable TBL
Sprinkler Monitor
TROUBLE
T
Class A TBL
Sprinkler Monitor
TROUBLE
T
Detailed Description:
Used to indicate sprinkler abnormal conditions such as
the operating of a PIV or OS&Y tamper switch. Must be used with normally
open contacts only.
Figure 5-25. SO Point Type
Pt. TYPE:
SC
Description:
Sprinkler Supv (normally closed)
Circuit Status
LCD Readout (2
nd
line)
LED
Normal
Sprinkler Monitor
SUPERVISORY
S
Limited Sprinkler
Monitor
NORMAL
Open Sprinkler
Monitor
TROUBLE
T
Short Sprinkler
Monitor
TROUBLE
T
Disable TBL
Sprinkler Monitor
TROUBLE
T
Class A TBL
Sprinkler Monitor
TROUBLE
T
Detailed Description:
Used the same as SO except the contacts monitored must
be normally closed and a shunt resistor used. This type assures the zone will
not go into alarm with multiple tamper valves activated. Refer to Field Wiring
Diagram page 7 if 4-Point IDC 565-473 is used; or page 11 for a 4-Point IDC
565-610.
Figure 5-26. SC Point Type
Continued on next page
Point Type Messages for Monitor Points,
Continued
Monitor Points
(continued)
Technical Manuals Online! - http://www.tech-man.com
Содержание LifeAlarm 4005 Series
Страница 2: ...this is blank text Technical Manuals Online http www tech man com ...
Страница 6: ...this is blank text Technical Manuals Online http www tech man com ...
Страница 58: ...this is blank text Technical Manuals Online http www tech man com ...
Страница 80: ...this is blank text Technical Manuals Online http www tech man com ...
Страница 129: ...6 9 SMPL Programming Continued SMPL Equations continued Technical Manuals Online http www tech man com ...
Страница 141: ...Technical Manuals Online http www tech man com ...
Страница 142: ...This Page intentionally left blank Technical Manuals Online http www tech man com ...