5-17
Pt. TYPE:
RWATER
Description:
Water Signal (on until Reset)
Circuit Status
LCD Readout (2
nd
line)
LED
Normal Waterflow
Signal
ON
Normal Waterflow
Signal
OFF
Normal Waterflow
Signal
CODING
Open Waterflow
Signal
TROUBLE
T
Short Waterflow
Signal
TROUBLE
T
Disable TBL
Waterflow Signal
TROUBLE
T
Off Auto TBL
Waterflow Signal
TROUBLE
T
Detailed Description:
Used in applications where a waterflow signal circuit is
required which will remain activated until the reset key is pressed. Activated
from any WATER point type.
Figure 5-44. RWATER Point Type
Pt. TYPE:
SUPV
Description:
Sprinkler Supervisory Signal (until
acknowledged)
Circuit Status
LCD Readout (2
nd
line)
LED
Normal Supervisory
Signal
ON
Normal Supervisory
Signal
OFF
Normal Supervisory
Signal
CODING
Open Supervisory
Signal
TROUBLE
T
Short Supervisory
Signal
TROUBLE
T
Disable TBL
Supervisory Signal
TROUBLE
T
Off Auto TBL
Supervisory Signal
TROUBLE
T
Detailed Description:
Used in applications where a supervisory signal circuit is
required which will remain ON until acknowledged.
Figure 5-45. SUPV Point Type
Continued on next page
Point Type Messages for Signal Points,
Continued
Signal Points
(continued)
Technical Manuals Online! - http://www.tech-man.com
Содержание LifeAlarm 4005 Series
Страница 2: ...this is blank text Technical Manuals Online http www tech man com ...
Страница 6: ...this is blank text Technical Manuals Online http www tech man com ...
Страница 58: ...this is blank text Technical Manuals Online http www tech man com ...
Страница 80: ...this is blank text Technical Manuals Online http www tech man com ...
Страница 129: ...6 9 SMPL Programming Continued SMPL Equations continued Technical Manuals Online http www tech man com ...
Страница 141: ...Technical Manuals Online http www tech man com ...
Страница 142: ...This Page intentionally left blank Technical Manuals Online http www tech man com ...