The Autocall panel will be programmed to activate command receiver address 6 whenever an
alarm silence operation is performed at the Autocall head-end. This will cause the XALIC to
indicate an abnormal status on M5-6-1. The following Custom Control equation will perform the
FACP’s alarm silence operation:
IN:
M5-6-1 ABNORMAL
; Alarm silence request from
Autocall panel
OUT:
TRACK P6 ON PRI=2,2
; Alarm silence pseudo point
END:
The Autocall panel will be programmed to activate command receiver address 7 whenever a
system reset operation is performed at the Autocall head-end. This will cause the XALIC to
indicate an abnormal status on M5-7-1. The following Custom Control equation will perform the
FACP’s system reset operation:
IN:
M5-7-1 ABNORMAL
; System Reset request from Autocall
panel
OUT:
TRACK P202 ON PRI=9,9
; System Reset pseudo point
END:
The Autocall panel will be programmed to activate command receiver addresses 8-11 whenever a
corresponding switch is activated in the panel. This will cause the XALIC to indicate an abnormal
status on points M5-8-1 through M5-11-1. Four Custom Control equations (one for each area)
will accomplish the disable function:
IN:
M5-8-1 ABNORMAL
; Disable area 1 request from
Autocall panel
OUT:
DISABLE L512
; Disable Panel Area 1
END:
The Autocall panel is programmed to activate command receiver address 12 whenever an alarm is
present in the system that did not come from the FACP. This causes the XALIC to indicate an
abnormal status on M5-12-1. No custom control is required to annunciate the alarm in the FACP.
M5-12-1 is programmed with the FIRE point type and an appropriate custom label such as
“ALARM IN Autocall SYSTEM”.
FACP XA Loop Slave Application Example,
Continued
Alarm Silence
System Reset
Disabling Areas
Alarm from Autocall
Panel