9
The setting of Jumper P3 determines whether the XALIC card detects and reports Earth faults to
the FACP. Earth Detect should only be enabled when the XALIC card is configured as the XA
Loop Master. Disable Earth Detect if the XALIC is being configured as an XA Loop Slave.
To enable Earth Detect, place the jumper in positions 1-2. To disable Earth Detect, place the
jumper in positions 2-3.
P3
Install Jumper on pins 1 and 2
for Earth Detect (XA Loop
Master Only). Install Jumper on
pins 2 and 3 for XA Loop Slave
Operation
1
2
3
Figure 5. Location of P3
Hardware Configuration,
Continued
Setting Jumper P3,
Earth Detect