6
The XALIC card address is set via DIP switch SW2, which is a bank of eight switches. From left
to right (see Figure 2, below) these switches are designated as SW2-1 through SW2-8. The
function of these switches is as follows:
SW2-1
. This switch sets the baud rate for the internal FACP communications line
running between the card and the FACP CPU. Set this switch to ON.
SW2-2 through SW2-8
. These switches set the card address. Refer to Table 3 for a
complete list of the switch settings for all of the possible card addresses.
Note:
You must set these switches to the value assigned to the card by the FACP
Programmer.
1
8
7
6
5
4
3
2
Figure 2. DIP Switch SW2
Continued on next page
Hardware Configuration
Setting DIP Switch
SW2, XALIC Card
Address
ON
OFF
DIP Switches SW2-2 through SW2-8
set the Card Address. Figure 2
shows an Address of 3.
4100 Comm. Baud Rate.
Switch (SW2-1)
Must Be Set to ON