Components — Motor Relay (MR-120)

 — Motor Relay (MR-120)

2.6 Motor Relay – MR-120 

Figure 11 

The MR-120 provides the output voltage for the actuators. The 
output at terminals “S” and “O” is designed in the pole changing 
technique. 

OPEN:

S = „+ “ O = „–“ 

CLOSE:

S = „–“ O = „+“

At the MR-120, you can find: 

• a  10 A fuse for the motor outputs
• two interfaces for actuators including separate line 

monitoring

• two contacts for ventilation function 

(e.g. button / thermostat)

• analog input (0 – 10 

V DC

 / 4 – 20 mA) for sequential 

triggering of actuators for ventilation purposes

• visual indicators:

– two white LEDs – triggering in “OPEN” / “CLOSE” 

direction

– yellow LED – “Failure”
– green LED – “OK”

2.6.1 Triggering of the load relays 

(“S” and “O” terminals)

The power output for the smoke and heat exhaust actuators is 
represented by two power relays which operate in pole chang-
ing technique to ensure OPEN 

CLOSE triggering. The 

M-SHEV motor outputs are fitted with overload protection. 
During mains failure mode, the relays drop out immediately as 
described in Chapter 2.2 “Fault mode” on page 9. They are on-
ly reactivated if an ALARM is triggered.

2.6.2 ALARM functions

2.6.2.a Open delay in alarm mode

The MR-120 allows you to set a start delay for 
certain applications (e.g. in combination with sun 
protection systems in front of windows). This 

ALARM triggering will be displayed immediately, received 
and processed and can be indicated by an MI-100 message 
interface. After the intended ALARM start delay time has 
been elapsed, the actuators move to the intended ALARM 
position.

2.6.2.b Priority function (Basic)

The MR-120 module operates as standard with 3 
priority levels for detection lines 1 (HE button), 2 
(smoke detector) and 3 (BMZ). When an as-

signed sensor interface is triggered, the MR-120 reacts by 
controlling the opening actuators in the OPEN direction. It is 
only possible to configure 1 common group of SI modules for 
all priority levels. 

This function allows you to define any priority sequence for 
the indicating lines. You can also invert every alarm trigger. 
When this setting is enabled, the allocated opening units are 
moved in the CLOSE direction instead of the usual OPEN 
direction, if an alarm is triggered.

2.6.2.c Priority function (Extended)

The extended priority function allows to configure 
an individual SI-100 group for each priority level. 

MR-120 

Motorrelais
Motor Relay

M–SHEV

®

Factory-configured

Motor

Fuse 

Internal

(internal

power supply)

Ventilation 1/
Ventilation 2

Motor 1| Motor 2

Analog

connection

input

BUS connection

INFORMATION

The triggering priorities and other functions can be 
modified on request using the SIMON LINK configuration 
software.

ATTENTION

This function can affect standards-compliant processing of 
alarm signals. Please check with the approval authorities 
regarding this function.

INFORMATION

If you change a setting at this point, please remember to 
apply a functionally identical setting to the ventilation func-
tions (see chapter 2.6.3.c “Open delay in vent mode” on 
page 14).

INFORMATION

If the ALARM release is inverted on the FAS indicating line 
(set to CLOSE), it is recommended to use the setting “FAS 
auto-reset” on the SI-100! (See Chapter 2.5.6 “Fire alarm 
system AUTORESET function” on page 12
.)
This has the advantage that the BMZ-ALARM is automati-
cally deleted after the release by the BMZ and the ventila-
tion function is available again via the ventilation button. 

Содержание M-SHEV Series

Страница 1: ...ily Copyright by SIMON PROtec Systems GmbH Subject to technical changes and errors All figures are exemplary Only valid with the supplementary sheet Safety instructions and warranty conditions Operati...

Страница 2: ...0 2 4 6 Technical data ZI 100 ZI1 10 2 5 Sensor Interface SI 100 11 2 5 1 Trigger or indicating lines line monitored 11 2 5 2 Indicators 11 2 5 3 ALARM mode reset 11 2 5 4 DIP switches 11 2 5 5 Reset...

Страница 3: ...time 17 2 7 3 Technical data MI 100 MI1 17 2 8 BUS Interface BI 100 optional 18 2 8 1 MODBUS 18 2 8 2 Digital inputs 18 2 8 3 Technical data BI 100 BI1 18 3 Mechanical connection 19 3 1 M SHEV 10 AP...

Страница 4: ...gulation electronics for the operation of 24 V DC actuators Ventilation signals from ventilation buttons wind rain detectors and alarm triggering of three monitored indicating lines emergency button S...

Страница 5: ...ties M SHEV 10 AP Dimensions W x H x D Weight including battery 14 3 kg Protection rating IP20 according to EN 60529 Housing Steel sheet powder coated Colour RAL 9010 Table 2 Mechanical properties M S...

Страница 6: ...tching power supply charging device battery are used cascaded The following figures may vary depending on the size of the housing and number of modules According to EN 12101 10 both the primary switch...

Страница 7: ...failure undervoltage of the power supply or if the primary power supply fails 2 1 4 Technical data rated values Table 6 Operating voltage continuous operation 230 V AC Permissible voltage range short...

Страница 8: ...Fuse character type T 3 15 A Charging voltage 26 7 27 9 V DC Charging current 1 1 A Interruption time no interruption LED indicator for mains operating state Continuous green light mains present LED i...

Страница 9: ...3 Internal BUS connection The individual modules of the M SHEV control panel are con nected to each other through the BUS connections RJ45 sockets 2 3 1 Terminal plugs AS 110 The AS 110 terminating pl...

Страница 10: ...evaluat ed independently of each other as normally open or normally closed Two 24 V DC terminals mains backup are available to connect the inputs The respective functions are shown in the connection p...

Страница 11: ...00 is provided with the following indicators Indicating line is triggered separate for B1 B2 and B3 red Failure faults of the SI 100 yellow OK operating state green 2 5 3 ALARM mode reset After a SI 1...

Страница 12: ...0 SI1 Table 17 Permissible voltage range 21 28 2 V DC Power consumption standby mode 10 20 mA Power consumption ALARM mode max 80 mA Emergency button connection 7 terminals OK Y M RZ RA B1 Smoke detec...

Страница 13: ...unction Basic The MR 120 module operates as standard with 3 priority levels for detection lines 1 HE button 2 smoke detector and 3 BMZ When an as signed sensor interface is triggered the MR 120 reacts...

Страница 14: ...as long as the respective direction button is pressed The actuators stop as soon as the button is released If the ventilation button is touched only briefly the ventilation command is switched to cont...

Страница 15: ...and closing times must be measured and then entered on site The connected actuators then move to the required position proportional to the applied supply voltage or current To ensure that this openin...

Страница 16: ...ntacts A statement always consists of three elements a logical statement no entry statement is true or NOT the statement is negated the origin of the statement and the statement Origin of the statemen...

Страница 17: ...ndition logical statement is true the dry contact relay is switched either as long as the condition remains true or for a preset time 1 second to 1 hour 2 7 2 c Hold time After reaching the condition...

Страница 18: ...o set the parity stop bits and a watchdog function If the MODBUS communication is lost the BI 100 goes into fault mode 2 8 2 Digital inputs There are 2 digital inputs A 24 V DC terminal mains is avail...

Страница 19: ...the housing s direct mounting points for the M SHEV see Figure 15 Mounting points back of housing or mount the four wall fixing lugs see Figure 16 Wall fixing lugs supplied to the housing and then ma...

Страница 20: ...10 AP Figure 18 M SHEV DANGER The system must be mounted by specialist personnel qualified electricians only All relevant national safety regulations and directives apply to mounting installation and...

Страница 21: ...h RM 2860 TH 4860 1 2 3 4 5 24V Wind Rain Digital Input GND E LZ A Z E 5 NO 1 2 3 NC Jumper Power Supply 4 e g central ventilation or other external control Mains Backup wind rain detector WTS OK Y M...

Страница 22: ...formation for motor cable empirical formula Wire cross section mm single cable length m x number of actuators x current consumption per actuator A 73 The DIN VDE 0100 and DIN VDE 0298 regulations cont...

Страница 23: ...rical fastening features i e it can be used on the right or left The lid can alternatively be equipped with a lock 5 2 M SHEV Place the pair of batteries on the bottom plate of the housing Connect the...

Страница 24: ...51 379368 0 Fax 49 0 851 379368 70 SIMON PROtec Deutschland GmbH Fraunhoferstra e 14 82152 Planegg Martinsried Tel 49 0 89 79170 11 Fax 49 0 89 79179 72 E Mail info simon protec de Internet www simon...

Отзывы: