2.6.1
Connecting up flue
Fig. 6 refers to the connection of the boilers
“25 OF C - 30 OF C”
to the flue or chimney
through smoke ducts.
When making the connection, in addition to
respecting the dimensions given, you are
recommended to use gas-tight materials
capable of resisting over time mechanical
stresses and the smokes heat.
At any point along the smoke duct, the tem-
perature of the combustion products must
be higher than the dew point. More than a
total of three changes of direction must not
be made, including the inlet connection to
the chimney/flue.
For any changes of direction use only cur-
ved pipe lengths.
Fig. 7 shows some applications of draught
terminals that ensure proper expulsion of
the combustion products, in case of
discharge through the wall.
2.7
“25 BFT TS” COAXIAL DUCT
The air inlet-smoke outlet assembly, code
8084813, is included in the standard supply
of the appliance complete with mounting
instructions.
With the pipe bend included in the kit, the
maximum length of the piping should not
exceed 3 meter.
The diagrams in fig. 8 illustrate a number of
examples of different coaxial outlets.
2.7.1
Coaxial flue diaphragm
The boiler is supplied as standard with a ø
81,0 diaphragm.
For C12-C42 discharge configurations:
install the diaphragm only when the length
of the coaxial duct is below 1 meter.
For C32 discharge configurations: use the
diaphragm in accordance with the instruc-
tions provided in figure 9.
2.7.2
Positioning the outlet terminals
The outlet terminals for forced-draught
appliances may be located in the external
Fig. 6
Fig. 7
C12
C32
C42
3
1
2
7
6
4
3
2
min 1
,3 m - max 5 m
8
x
y
x + y = max 3,5 m
"25"
x + y = max 3,0 m
"30-35"
max 3,5 m
"25"
max 3,0 m
"30-35"
Fig. 8
KEY
1
Coaxial flue kit L. 810 code 8084813
2 a Extension L. 1000 code 8096103
2 b Extension L. 500 code 8096102
3
Vertical extension L. 200 code 8086908
4
Additional 90° curve code 8095801
6
Articulated tile code 8091300
7
Roof outlet terminal L. 1284 code 8091200
8
Vertical condensation collector L. 200 code 8092803
IMPORTANT:
– Each additional 90° curve
installed reduces the availa-
ble length by 0.90 metres.
– Each additional 45° curve
installed reduces the availa-
ble length by 0.45 metres.
– It is advisable to assemble
the condensation collector
(8) on ver tical segments
e x c e e d i n g 2 m e t r e s i n
length and to limit maximum
length to 4 metres.
x + y = max 3 m
max 3 m
Fig. 9
For C32 discharge configurations: use the diaphragm as specified
below, taking into account the length of the duct and avoiding bends:
Installations with vertical
Installations with vertical
extension L. 200 code 8086908
condensation collector code 8092803
Diaphragm
Without
Diaphragm
Without
ø 81
diaphragm
ø 81
diaphragm
L min = 1,3 m
L min = 2,5 m
L min = 1,3 m
L min = 2 m
L max = 2,5 m
L max = 5 m
L max = 2 m
L max = 4 m
Содержание PLANET 25 BFT TS
Страница 1: ...IT ES PT GB RO RUS CERTIFICAZIONE DEL SISTEMA DI QUALITA AZIENDALE Planet...
Страница 2: ......
Страница 72: ...70 IT ES PT GB RO RUS...
Страница 106: ...104 IT ES PT GB RO RUS...
Страница 140: ...138 IT ES PT GB RO RUS...
Страница 208: ...206 IT ES PT GB RO RUS...
Страница 209: ......
Страница 210: ......
Страница 211: ......
Страница 212: ...Fonderie Sime S p A Via Garbo 27 37045 Legnago Vr Tel 39 0442 631111 Fax 39 0442 631292 www sime it...