2.7
POSITIONING
THE OUTLET TERMINALS
The outlet terminals for forced-draught
appliances may be located in the external
perimeter walls of the building.
To provide some indications of possible solu-
tions,
Table 3
gives the minimum distances
to be observed, with reference to the type
of building shown in fig. 6.
2.8
SEPARATE PIPES ø 80
(Optional alternative twin
pipe system)
A special kit may be used to separate the
10
Terminal position
Minimum spacing
A
Directly below an openable window, air vent
or any other ventilation opening
300 mm
12 in
B
Below guttering, drain pipes or soil pipes
75 mm
3 in
C/D
Below eaves, balconies or carport roof
200 mm
8 in
E
From vertical drain pipes or soil pipes
75 mm
3 in
F
From internal or external corners
300 mm
12 in
G
Above adjacent ground, roof or balcony level
300 mm
12 in
H
From a surface facing the terminal
600 mm
24 in
I
From a terminal facing the terminal
1,200 mm
48 in
J
From an opening in the carport
(eg door, window into dwelling)
1,200 mm
48 in
K
Vertically from a terminal on the same wall
1,500 mm 60 in
L
Horizontally from a terminal on the same wall
300 mm 12 in
M
Horizontally from a vertical terminal to a wall
300 mm 12 in
N
Horizontally from an openable window or other opening 300 mm 12 in
P
Above an openable window or other opening
300 mm
12 in
TABLE 3
– If the terminal discharges into a pathway or passageway check that combus-
tion products will not cause nuisance and that the terminal will not obstruct
the passageway.
– Where the lowest part of the terminal is fitted less than 2 m (78 in) above
ground, above a balcony or above a flat roof to which people have access, the
terminal MUST be protected by a purpose designed guard. Terminal guards
are available from Quinnell, Barrett, and Quinnell, Old Kent Road, London. State
model C2, (G.C. Part No 382946).
– Where the terminal is fitted within 850 mm (34 in) of a plastic or painted gut-
ter, or 450 mm (18 in) of painted eaves, an aluminium shield at least 1,500
mm (59 in) long must be fitted to the underside of the painted surface.
– The air inlet/outlet flue duct MUST NOT be closer than 25 mm (1 in) to com-
bustible material.
– In certain weather conditions the terminal may emit a plume of steam. This is
normal but positions where this would cause a nuisance should be avoided.