29
6.10
Condensate outlet/collection
In order to collect the condensate, it is recommended that:
– the appliance condensate outlets and the smoke outlet are
ducted
– a neutralising device is prearranged
– the outlet incline is
>3%
.
m
CAUTION
– The condensate outlet duct must be airtight, suitably
sized to that of the siphon and must not be restricted
at any point.
– The condensate outlet must be constructed in full
compliance of the National or Local regulations in
force.
– Before commissioning the appliance, fill the siphon
with water.
6.11
Gas supply
MURELLE.HT
boilers leave the factory specifically prearranged for
G20 gas or G31. The G20 models can be converted to function with
G31 using the "specific nozzle kit" (optional) provided by
Sime
on
request separately from the boiler.
If changing the type of gas to be used, carry out the entire
"GAS
CONVERSION"
phase of the appliance.
The boiler must be connected to the gas mains in full compliance
with the installation standards in force in the country where the
appliance will be used.
Before connecting the boiler to the gas mains, the user must en-
sure that:
– the type of gas is correct for the appliance
– the pipes are clean
– the gas supply pipe is the same dimension as or greater than
that of the boiler fitting (G3/4") and with a load loss less than
or equal to that contemplated between the gas mains and the
boiler.
a
WARNING
Once installation has been completed, check that the
joints are air tight as indicated in the installation Stand-
ards.
m
CAUTION
It is recommended that the gas line has a suitable filter.
m
CAUTION
If the gas supply is changed from G20 to G31, mark the
box on the TECHNICAL DATA PLATE.
X
G31 - 37 mbar