10
Adjustment of air flow
1
Grease filters
Remove the grease filters (Fig. 11/2).
1- Damper
2- Measuring
To measure the air flow, unscrew the screw (M3X8 YHB) from the
1- Damper
2- Measuring
Now connect the measuring device to the measuring socket
To adjust the product to the desired condition, use the setting
tables.
Sizing information & Balancing information
Sizing data (For calculations)
50 Pa
100 Pa
Basic ventilation:
20 l/s (72 m3/h)
20 l/s (72 m3/h)
Pressure
60 Pa
120 Pa
Damper position
G 5.3
G 4.3
Sound pressure
(Lpa)
27 dBA
33 dBA
Forced ventilation:
40 l/s (144 m3/h)
40 l/s (144 m3/h)
Pressure
50 Pa
100 Pa
Damper position
F 5
F 3
Sound pressure
(Lpa)
27 dBA
33 dBA
1
Fig. 11
1
2
Fig. 12
1
2
Pa
Fig. 13
Adjustment of air flow
24.07.2020
17