Installation
25
users manual inverter SE2.8i - SE3.8i - SE4i - SE5i
2.3.2.2 Connection of the DC wires for Positive Ground Arrays
The SE inverter also supports PV arrays with positive ground for some applications. As shown in the figure 2.3.2.2.1, the JP14 and JP15
jumpers are placed on the higher positions to set to the positive ground. And the red DC wire is connected to DCIN- terminal and the black
DC wire is connected to DCIN+ terminal. In this case the positive polarity of the DC input voltage from the PV string shall be connected to
GROUNDED CONDUCTOR terminal and the negative polarity of the DC input voltage from the PV string shall be connected to UNGROUNDED
CONDUCTOR terminal as shown in the figure 2.3.2.2.2.
Fig 2.3.2.2.1 Positive Ground Setting and DC wire connections
Fig 2.3.2.2.2 DC terminal blocks for DC cable connection in Positive Ground