MSA510/1
Trouble shooting English
MSA510/1 · Date
04.05.2016 · Art.
No.
83520 · Mod.
status
38/16
38
Command
Length Reply
Description
s
1/2
">"
Set device to original state; default values
(alignment is retained!):
counting direction: upward
code: Gray code
zero-point value: 0
resolution: 0.01 mm
tx
2/2
">"
write counting direction (non-volatile)
x=0: upward
x=1: downward
ux
2/2
"xy"
read out internal values (only for use in
our factory!)
vklmnop
7/2
">"
write baud rate (volatile) "klmnop":
004800, 009600, 019200, 038400, 057200
oder 115200
w
1/3
"xyz"
read out hexadecimal position value
y
1/6
"0x3b>"
read out flag register (for internal pur-
poses)
z
1/10
"+1234567>" read out ASCII position value
7 Trouble shooting
Below are some typical errors which may occur during installation and
operation:
•
Magnetic tape wrongly mounted, active side below (see chapter
).
•
The masking tape provided was not used for protecting the magnetic
tape. The masking tape must not be magnetizable.
•
Magnetic sensor not or incorrectly connected.
•
The distance tolerances were not observed over the whole measuring
length or the sensor scrapes the magnetic tape (see
•
Cable interrupted / squeezed / cut by sharp edges.
•
The magnetic sensor has been mounted with the active side turned
away from the tape (see
,
•
Magnetic sensor has not been aligned according to
•
Magnetic fields near the measuring surface distort the measuring val-
ues. If required, pro-vide for adequate screening.
•
Wrong measuring values due to EMC interferences (see chapter
).