14. Maintenance
Clean the instrument case and front panel with a soft cloth and mild liquid soap solution.
15. Troubleshooting
Dial Selection
•
The analog display shows percentage of batch complete.
•
The reversible dial scales are 0 to100%, or 100 to 0%.
•
The instrument is shipped with the 0 to 100% scale installed.
•
Reverse the face plate for either scale.
•
Meter deflection is fixed from left to right.
B
A
D
C
ENTER
ALARM 1
ALARM 2
0
100
ALARM 1
ALARM 2
100
%
Batch
0
0 - 100
%
Batch
Display
Problem
Solution
-- -- -- --Gallons/m
Display tim ebase too large
Change flow tim ebase (S=Seconds, M=Minutes, H=Hours, D=Days) in
<ENTER> to START
CALIBRATE m enu to a sm aller value (e.g. GPD to GPM)
Tim e Left - - - m in
Rem aining batch time greater than
<ENTER> to Stop
999 m inutes (overrange)
-0001.8 Gallons
Flow rate detected after batch end
Repair leaky or stuck flow shuttoff valve.
<ENTER> to Start
Flow K-Factor
Flow (batch) display K-Factor dan noEnter K-Factor greater than zero (sec. 10.2D)
can not be zero
be zero
Total K-Factor
Totalizer K-Factor can not be
Enter K-Factor greater than zero (sec. 9.2E)
can not be zero
zero
Must be between
Missing signal tim e delay m ust be se Enter m issing signal tim e delay within 0.10 - 999 seconds (sec. 10.4I)
0.10 - 999
for 0.10 - 999 seconds
Overrun Volum e
Overrun alarm volum etric setting
Enter overrun alarm volumetric setpoint within 0.00100 - 999999.)
can not be zero
m ust be within 0.00100 - 999999.
engineering units (sec. 10.4H
engineering units
Power Failure
Instrum ent power interrupted during Use RIGHT arrow key to select "Resum e" or "Clear". Selecting resum e will
Resum e Clear
active batch process
continue the batch from the point where the power interruption occurred.
Selecting clear will clear the power failure. After your selection has been
m ade, press ENTER to continue.
Setup Read Error
Power fault occurred while saving
Press any key to reload factory defaults then reprogram flow system setup
Press any Key
setup m enu entry
param eters. Note: Totalizer displays rem ain undistrubed and will
resum e after instrum ent reset.
Display will show actual rem aining m inutes after the rem aining batch tim e is
less than 999 m inutes