background image

4 of 12

ÐSIGNET 

5600 Batch Controller

   Current Output:
     End of Batch

   Option Contact:
     End of Batch

   Option Contact:
   Overrun Alarm

  Option Contact:
     Two Stage

0% 

100%

Batch running...

4 mA

20 mA

valve

valve

0 mA

20 mA

0%

100%

500ms

Batch running...

• Counter/End of Batch Pulse Output (sec. 6):  In advanced mode, the output can be
configured as either a  counter pulse output (sec. 9.1) or as an end of batch pulse

output.  When configured as an end of batch pulse, the output emits a 500 millisecond pulse at the
completion of every batch.  The output is a open collector type which requires an external pull up resistor
and power supply for external counter use (sec. 6).

Option Contact - Two Stage Shutdown (sec. 7A):

 

 

This function is designed to prevent over filling or to minimize water hammer.

Both the batch and the option contact are energized when the batch starts. The option contact then de-energizes at a programmed batch percent-

age,  forcing flow through a smaller bypass line to reduce the fill rate.  After the entire batch is measured, the batch contact de-
energizes, completing the sequence.  Front keypad and remote START, STOP, and RESUME
inputs (sec. 5) also control the option contact.  The front panel contact indicator turns on when

the option contact is energized.

• Option Contact - Overrun Alarm (sec. 7B):

  This function provides overrun alarm

capability for detecting a leaky or stuck valve.  If the programmed batch overrun volume is measured after the batch

ends, the option contact is energized and the front panel contact indicator turns on, alarming
the operator that the flow shut off valve is leaking or stuck open.  To cancel alarm, press the
ENTER key (or remote STOP switch) once.  The overrun alarm will retrigger if the condition
persists.

• Option Contact - End of Batch Pulse (sec. 7C):

  This function is designed to trigger an external batch counter or second 5600 Batch Controller at

the end of a batch.  The option contact is energized for 500 milliseconds at the end of every batch cycle.  An external power
supply switched through the option contact's common (COM) and normally open (NO) terminal provides a pulse for triggering
these devices.

• Option Contact - Missing Signal Alarm (sec. 7B):

  The missing signal alarm represents a missing sensor signal after batch

start-up.  An adjustable time delay entry (in seconds) is offered which specifies how long the instrument will wait after batch
start-up before initiating the missing signal alarm.  See simple operation mode (sec. 9.1) for alarm operation details.

• Option Contact On/Off (sec. 10.4H):

  This function enables or disables the option contact and front panel option LED.

When the option contact is configured "Off", the option contact and front panel LED are disabled.

• Missing Signal Alarm On/Off (sec. 10.4H):

Missing signal alarm is always enabled (factory default sec. 9.1) even if the option contact is selected to be a different function.
This function is designed to completely disable the missing signal alarm, if desired.  NOTE:  If disabled, the batch contact is
NOT affected and will NOT signal the operator or stop the running batch if there is a problem.

• Current Output - Batch Completion (sec. 8A):  

In advanced mode, the current output

functions identical to the simple operation mode. See the simple operation mode explanation
above.

• Current Output - Valve Control (sec. 8B):

  This function is designed for use with a George Fischer electric

actuator with PE 22P positioner for preventing overflow or minimizing water hammer.  When a batch starts, the
current output is held at 20 mA, forcing the PE 22P positioner to the full open valve position.  Near batch end, the output gradually ramps downward

to slow the flowrate, then drops to 4 mA closing the valve and ending the batch.  Front keypad and remote START, STOP, and
RESUME inputs also control the output (sec. 5).  A STOP command any time during a batch
sequence will force the output to 4 mA and close the PE 22P positioner.  (Note:  for optimum
performance, the batch process should last at least 1 minute!)

• Current Output - End of Batch (sec. 8C):

  This function is designed to trigger a second 5600 batch controller's

remote START input for a second batching stage.  When the batch starts, the current output remains at 0 mA until the end of the batch, then jumps to
20 mA for 500 milliseconds.  The 500 millisecond current pulse triggers the second 5600's remote START terminal to start the second batch stage.

batch contact 

Option contact

0%

100%

Overrun

Batch running...

batch contact 

Option contact

0%

100%

90%

Batch running...

   Option Contact:
   Missing Signal

   Option Contact:
           Off

   Current Output:
    Valve Control

   Current Output:
 Batch Completion

 Missing Signal        
 Alarm:       On

batch contact 

Option contact

0%

100%

500ms

Batch running...

Содержание GF 5600

Страница 1: ...mpedance sec 8A is affected by the supply voltage To reduce the possibility of noise interference isolate AC power lines from signal lines Double Insulated DC or AC power Contents 1 Wiring terminals 2 Power Connection 3 Compatible Sensor Wiring 4 Batch Contact Wiring 5 Remote Control Wiring 6 End of Batch Counter Pulse Output Wiring 7 Option Contact Wiring Options Technical Notes To reduce the pos...

Страница 2: ... EOB output External Counter Gnd IN 5 30 VDC 10 kΩ Rsm RTN Start Stop Remote Gnd CNT EOB output First 5600 Second 5600 B Daisy chaining two 5600 batch controllers together A External counter connection 5600 Terminals Technical Notes Use 2 conductor shielded twisted pair cable for output lines up to 30 m 100 ft max 6 End of Batch Counter Pulse Output Wiring See section 9 for simple and advanced mod...

Страница 3: ...on sec 8A This function is offered in the simple or advanced operation mode The output is a linear increase from 4 mA at batch start to 20 mA at batch end 9 2 Advanced Operation Mode Batch Contact sec 4 The batch contact is dedicated for on off control and is either manually or automatically compensated for batch overrun Manual overrun compensation allows the operator to compensate for valve closu...

Страница 4: ... batch start up An adjustable time delay entry in seconds is offered which specifies how long the instrument will wait after batch start up before initiating the missing signal alarm See simple operation mode sec 9 1 for alarm operation details Option Contact On Off sec 10 4H This function enables or disables the option contact and front panel option LED When the option contact is configured Off t...

Страница 5: ...t 1 min ENTER to Stop 10 Menu Functions Note BATCH VIEW Menu steps B E MUST be selected for CALIBRATE Menu sec 10 2 or OPTIONS Menu sec 10 4 access OPTIONS CALIBRATE VIEW 2s 5s Press hold for access ENTER 10 1 BATCH VIEW Menu example Menu steps B E cannot be accessed when a batch is running Press ENTER to stop batch cycle Steps B E MUST be selected for CALIBRATE Menu sec 10 2 or OPTIONS Menu sec 1...

Страница 6: ...ctor Auto Calibrate ENTER to Start Auto Calibrate Procedure Accurate reference container required See procedure sec 10 3 Start Stop ENTER ENTER ENTER Save Save Enter volume A Reenter volume Batch Units Liter Flow Time Base s S m M h H d D ENTER D Batch K Factor 60 000 Set batch K Factor 0 0001 99999 see note Batch K Factor G Last CAL Sets user defined date Last calibration E Set totalizer units Az...

Страница 7: ...Alarm 1 00000 Gallons Set overrun alarm volume 0 00001 999999 Option Contact Overrun Alarm 0002 50 Gallons Overrun Alarm mode selected Missing Signal Alarm On Missing signal alarm On or Off Option Contact Missing Signal Alarm Off On Two Stage Overrun Alarm End of Batch or Off mode selected ENTER SAVING briefly displays Option Contact End of Batch End of Batch Option Contact Two Stage Two Stage Opt...

Страница 8: ...ading Input Optically isolated Enclosure Rating NEMA 4X IP65 front Dimensions 1 4 DIN 96 x 96 x 88 mm 3 8 x 3 8 x 3 5 in Case materials ABS plastic Keypad material Sealed 4 key silicone rubber Weight Approximately 500 g 18 oz Display Type Microprocessor controlled air core meter movement and alphanumeric 2 x 16 LCD Update rate 200 ms Contrast User selected Alarm annunciators green batch LED left r...

Страница 9: ...24 V 10 W GF SIGNET Model 3 5600 Rsm RTN Gnd Start Stop Remote CNT EOB output Current output Dimensions 13 Quick Reference Menu Parameters 13 1 VIEW Menu Setup Parameters sec 10 1 Menu Parameters Factory Default Range Display Description Press ENTER to start stop or resume batch Programmed batch volume Resettable totalizer Permanent totalizer Overrun mode Overrun volume See programmed batch volume...

Страница 10: ... Batch Count up or down 3 Off Advanced Totalizer Manual 0 00000 Gallons Missing signal 95 0 1 00000 Gallons On 0 10 seconds Batch Completion Count up A B C D E F G H I J K Contrast 3 Total Decimal Lock OFF Operating Mode Advanced Pulse Output Totalizer Display Decimal Option Contact Missing Signal Current Output BatchCompletion Two Stage Setpoint 95 0 Missing Signal Delay 30 0 sec Count Direction ...

Страница 11: ... 10 2D can not be zero be zero Total K Factor Totalizer K Factor can not be Enter K Factor greater than zero sec 9 2E can not be zero zero Must be between Missing signal time delay must be se Enter missing signal time delay within 0 10 999 seconds sec 10 4I 0 10 999 for 0 10 999 seconds Overrun Volume Overrun alarm volumetric setting Enter overrun alarm volumetric setpoint within 0 00100 999999 ca...

Страница 12: ...nue El Monte CA 91731 2882 U S A Tel 626 571 2770 Fax 626 573 2057 For Worldwide Sales and Service visit our website www gfsignet com Or call in the U S 800 854 4090 GEORGE FISCHER Piping Systems 3 5600 090 1 D 6 03 English Signet Scientific Company 2001 Printed in U S A on recycled paper ...

Отзывы: