CAUTION!

Remove power to unit before wiring input and
output connections.

Follow instructions carefully to avoid personal
injury.

2.   Power Connection

CAUTION!

Never connect 115 VAC or 230 VAC to rear power
terminals.  High voltage AC will damage instrument and
void warranty.

3.  Compatible Sensor Wiring

4.  Batch Contact Wiring

See section 9 for simple and advanced mode configuration
options.

-

+

12-24 V

10 W

-

+

12 - 24 VDC

OR

12 - 24 VAC

5600 
Terminals

External power
supply

Red

Black

Shld.

2000
2507
2536
2540
2550
Vortex*

Red

Black

Shld.

515 
525 
2517

+GF+ SIGNET

 Sensors:

Open Collector 
Sensor

Std. Sensor

Freq. IN

Sen. Pwr.

Freq. IN 

Iso. Gnd

5600 
Terminals

NC

C

NO

NC

C

NO

Batch

Option

flow

AC or DC

power 

valve

5600 
Terminals

Technical Notes:

Maximum alarm contact ratings:  5 A @ 30 VDC, 5 A @ 125
VAC, or 3 A @ 250 VAC

• To reduce the possibility of noise interference, isolate AC power

lines from signal lines.

Technical Notes:

Maximum 4-20 mA loop impedance (sec. 8A) is affected by the
supply voltage.

To reduce the possibility of noise interference, isolate AC
power lines from signal lines.

= Double Insulated

= DC or AC power

Contents

1.

Wiring terminals

2.

Power Connection

3.

Compatible Sensor Wiring

4.

Batch Contact Wiring

5.

Remote Control Wiring

6.

End of Batch/Counter Pulse Output Wiring

7.

Option Contact Wiring Options

Technical Notes:

To reduce the possibility of noise interference, route sensor
cable )away from AC power lines.

• *Vortex sensor or system frequency output

8.

Current Output Wiring Options

9.

5600 Operation Modes

10.

Menu Functions

11.

Parts and Accessories

12.

Specifications

13.

Quick Reference Menu Parameters

14.

Maintenance

15.

Troubleshooting

Total
reset

AUX

output

PLS

output

1

2

Gnd

+

+

-

+

Gnd

Freq. IN

Sen. Pwr.

Freq. IN

Iso. Gnd

Std. Sensor

        

  Patent No.  D376,328

     Flow

Open Collector 
Sensor

12-24 V

10 W

LISTED
77CJ

UL

 1   2   3   4   5   6

 1   2   3   4

 1   2

 1   2

Total
reset

AUX

output

PLS

output

1

2

Gnd

+

+

-

+

Gnd

Freq. IN

Sen. Pwr.

Freq. IN

Iso. Gnd

Std. Sensor

        

  Patent No.  D376,328

     Flow

Open Collector 
Sensor

12-24 V

10 W

LISTED
77CJ

UL

 1   2   3   4   5   6

 1   2   3   4

 1   2

1.

2.

3.

Remove terminal blocks for easy wiring.

1.

Wiring terminals

*3-5600.090-1*

3-5600.090-1 (Rev. D-6/03) English

Содержание GF 5600

Страница 1: ...mpedance sec 8A is affected by the supply voltage To reduce the possibility of noise interference isolate AC power lines from signal lines Double Insulated DC or AC power Contents 1 Wiring terminals 2 Power Connection 3 Compatible Sensor Wiring 4 Batch Contact Wiring 5 Remote Control Wiring 6 End of Batch Counter Pulse Output Wiring 7 Option Contact Wiring Options Technical Notes To reduce the pos...

Страница 2: ... EOB output External Counter Gnd IN 5 30 VDC 10 kΩ Rsm RTN Start Stop Remote Gnd CNT EOB output First 5600 Second 5600 B Daisy chaining two 5600 batch controllers together A External counter connection 5600 Terminals Technical Notes Use 2 conductor shielded twisted pair cable for output lines up to 30 m 100 ft max 6 End of Batch Counter Pulse Output Wiring See section 9 for simple and advanced mod...

Страница 3: ...on sec 8A This function is offered in the simple or advanced operation mode The output is a linear increase from 4 mA at batch start to 20 mA at batch end 9 2 Advanced Operation Mode Batch Contact sec 4 The batch contact is dedicated for on off control and is either manually or automatically compensated for batch overrun Manual overrun compensation allows the operator to compensate for valve closu...

Страница 4: ... batch start up An adjustable time delay entry in seconds is offered which specifies how long the instrument will wait after batch start up before initiating the missing signal alarm See simple operation mode sec 9 1 for alarm operation details Option Contact On Off sec 10 4H This function enables or disables the option contact and front panel option LED When the option contact is configured Off t...

Страница 5: ...t 1 min ENTER to Stop 10 Menu Functions Note BATCH VIEW Menu steps B E MUST be selected for CALIBRATE Menu sec 10 2 or OPTIONS Menu sec 10 4 access OPTIONS CALIBRATE VIEW 2s 5s Press hold for access ENTER 10 1 BATCH VIEW Menu example Menu steps B E cannot be accessed when a batch is running Press ENTER to stop batch cycle Steps B E MUST be selected for CALIBRATE Menu sec 10 2 or OPTIONS Menu sec 1...

Страница 6: ...ctor Auto Calibrate ENTER to Start Auto Calibrate Procedure Accurate reference container required See procedure sec 10 3 Start Stop ENTER ENTER ENTER Save Save Enter volume A Reenter volume Batch Units Liter Flow Time Base s S m M h H d D ENTER D Batch K Factor 60 000 Set batch K Factor 0 0001 99999 see note Batch K Factor G Last CAL Sets user defined date Last calibration E Set totalizer units Az...

Страница 7: ...Alarm 1 00000 Gallons Set overrun alarm volume 0 00001 999999 Option Contact Overrun Alarm 0002 50 Gallons Overrun Alarm mode selected Missing Signal Alarm On Missing signal alarm On or Off Option Contact Missing Signal Alarm Off On Two Stage Overrun Alarm End of Batch or Off mode selected ENTER SAVING briefly displays Option Contact End of Batch End of Batch Option Contact Two Stage Two Stage Opt...

Страница 8: ...ading Input Optically isolated Enclosure Rating NEMA 4X IP65 front Dimensions 1 4 DIN 96 x 96 x 88 mm 3 8 x 3 8 x 3 5 in Case materials ABS plastic Keypad material Sealed 4 key silicone rubber Weight Approximately 500 g 18 oz Display Type Microprocessor controlled air core meter movement and alphanumeric 2 x 16 LCD Update rate 200 ms Contrast User selected Alarm annunciators green batch LED left r...

Страница 9: ...24 V 10 W GF SIGNET Model 3 5600 Rsm RTN Gnd Start Stop Remote CNT EOB output Current output Dimensions 13 Quick Reference Menu Parameters 13 1 VIEW Menu Setup Parameters sec 10 1 Menu Parameters Factory Default Range Display Description Press ENTER to start stop or resume batch Programmed batch volume Resettable totalizer Permanent totalizer Overrun mode Overrun volume See programmed batch volume...

Страница 10: ... Batch Count up or down 3 Off Advanced Totalizer Manual 0 00000 Gallons Missing signal 95 0 1 00000 Gallons On 0 10 seconds Batch Completion Count up A B C D E F G H I J K Contrast 3 Total Decimal Lock OFF Operating Mode Advanced Pulse Output Totalizer Display Decimal Option Contact Missing Signal Current Output BatchCompletion Two Stage Setpoint 95 0 Missing Signal Delay 30 0 sec Count Direction ...

Страница 11: ... 10 2D can not be zero be zero Total K Factor Totalizer K Factor can not be Enter K Factor greater than zero sec 9 2E can not be zero zero Must be between Missing signal time delay must be se Enter missing signal time delay within 0 10 999 seconds sec 10 4I 0 10 999 for 0 10 999 seconds Overrun Volume Overrun alarm volumetric setting Enter overrun alarm volumetric setpoint within 0 00100 999999 ca...

Страница 12: ...nue El Monte CA 91731 2882 U S A Tel 626 571 2770 Fax 626 573 2057 For Worldwide Sales and Service visit our website www gfsignet com Or call in the U S 800 854 4090 GEORGE FISCHER Piping Systems 3 5600 090 1 D 6 03 English Signet Scientific Company 2001 Printed in U S A on recycled paper ...

Отзывы: