1 of 12
ÐSIGNET
5600 Batch Controller
‡ SIGNET 5600 Batch Controller
ENGLISH
CAUTION!
•
Remove power to unit before wiring input and
output connections.
•
Follow instructions carefully to avoid personal
injury.
2. Power Connection
CAUTION!
Never connect 115 VAC or 230 VAC to rear power
terminals. High voltage AC will damage instrument and
void warranty.
3. Compatible Sensor Wiring
4. Batch Contact Wiring
See section 9 for simple and advanced mode configuration
options.
-
+
12-24 V
10 W
-
+
12 - 24 VDC
OR
12 - 24 VAC
5600
Terminals
External power
supply
Red
Black
Shld.
2000
2507
2536
2540
2550
Vortex*
Red
Black
Shld.
515
525
2517
+GF+ SIGNET
Sensors:
Open Collector
Sensor
Std. Sensor
Freq. IN
Sen. Pwr.
Freq. IN
Iso. Gnd
5600
Terminals
NC
C
NO
NC
C
NO
Batch
Option
flow
AC or DC
power
valve
5600
Terminals
Technical Notes:
•
Maximum alarm contact ratings: 5 A @ 30 VDC, 5 A @ 125
VAC, or 3 A @ 250 VAC
• To reduce the possibility of noise interference, isolate AC power
lines from signal lines.
Technical Notes:
•
Maximum 4-20 mA loop impedance (sec. 8A) is affected by the
supply voltage.
•
To reduce the possibility of noise interference, isolate AC
power lines from signal lines.
= Double Insulated
= DC or AC power
Contents
1.
Wiring terminals
2.
Power Connection
3.
Compatible Sensor Wiring
4.
Batch Contact Wiring
5.
Remote Control Wiring
6.
End of Batch/Counter Pulse Output Wiring
7.
Option Contact Wiring Options
Technical Notes:
•
To reduce the possibility of noise interference, route sensor
cable )away from AC power lines.
• *Vortex sensor or system frequency output
8.
Current Output Wiring Options
9.
5600 Operation Modes
10.
Menu Functions
11.
Parts and Accessories
12.
Specifications
13.
Quick Reference Menu Parameters
14.
Maintenance
15.
Troubleshooting
Total
reset
AUX
output
PLS
output
1
2
Gnd
+
+
-
+
Gnd
Freq. IN
Sen. Pwr.
Freq. IN
Iso. Gnd
Std. Sensor
Patent No. D376,328
Flow
Open Collector
Sensor
12-24 V
10 W
LISTED
77CJ
UL
1 2 3 4 5 6
1 2 3 4
1 2
1 2
Total
reset
AUX
output
PLS
output
1
2
Gnd
+
+
-
+
Gnd
Freq. IN
Sen. Pwr.
Freq. IN
Iso. Gnd
Std. Sensor
Patent No. D376,328
Flow
Open Collector
Sensor
12-24 V
10 W
LISTED
77CJ
UL
1 2 3 4 5 6
1 2 3 4
1 2
1.
2.
3.
•
Remove terminal blocks for easy wiring.
1.
Wiring terminals
*3-5600.090-1*
3-5600.090-1 (Rev. D-6/03) English