9900 Transmitter
Technical Notes:
• The cable length from the
8058 to the 9900 must not
exceed 60 m (200 ft).
• When using the 8058-2,
connect the loop source to
Channel 1 input ONLY.
• See the 8058 manual for
more information.
Wiring for:
Input
4-to-20 mA
Output
S
3
L
Signet 8058 i-Go™
4-20 mA to S
3
L Converter
+GF+
4-20 mA input
S
3
L Output
Signet 8058 i-Go™
4-20 mA to S
3
L Converter
Output
S
3
L
S
3
L Output
DA
T
A
GND
SHLD
V+
8058-1
close-up
Black
Red
Shield
White
8058-1
9900 S
3
L Inputs
4-20 mA
Input
N/C 3
Loop1 - 2
Loop1 + 1
+GF+
S L
Output
3
7 +5VDC
8 S L
9 GND
3
8058 i-Go™
4-20mA
to S
3
L
Converter
3-8058.610D
35
VDC
MAX
N/C 6
Loop2 - 5
Loop2+ 4
3 2 1
6 5 4
7 8 9
Lo
op1
PWR
+GF
+
N/C
S
L
DA
TA
3
Loop2
PWR
Sign
et 80
58
8058-2
7 8 9
N/C
S L
DATA
3
close-up
8058-2
DA
T
A
GND
V+
SHLD
BLACK
WHITE
RED
9900 S
3
L Inputs
Technical Notes:
• Use three conductor shielded
cable for sensor cable splices
up to 305 m (1000 ft) max.
• Maintain cable shield through
cable splice.
• Route sensor cable away
from AC power lines.
• Connect the silver (shield)
wire to earth ground in case
of EMI noise interference.
Technical Notes:
• The 2850 has no SHIELD wire.
• To work correctly with the
9900, the 2850 must be set
for the custom cell constant or
the actual probe cell constant
and the 9900 set for a 1.0 cell
constant.
Wiring for:
* 2551-XX-21, -41
Display Magmeter
2250
2350
2450
2551*
2750/2751
2850
Black
Red
Shield
White
V+
DA
T
A
GND
SHLD
9900 S
3
L Inputs
NOTE:
The 2850 has no SHIELD wire.
Sensor Wiring