53
9900 Transmitter
Custom point #10
3000 gal.
Custom point #1
0 gal.
Custom point #2
45 gal.
Custom point #3
118 gal.
Custom point #4
Custom point #5
250 gal.
Custom point #9
1300 gal.
Custom point #6
380 gal.
Custom point #7
700 gal.
Custom point #8
1000 gal.
160 gal.
Level and Volume Calculation in Custom Shaped Vessels
In the LEVEL/VOLUME menu, if Custom Shape is selected in the INPUT menu, you can de
fi
ne
from three to ten Custom Points to establish the relationship of level to volume in the vessel.
●
Select Manual Level Measurement mode to edit both level and volume data (dry con
fi
guration).
●
Select Automatic Level Measurement mode to accept the sensor measurement of the Level,
while you assign a volumetric value to each custom point (wet con
fi
guration).
●
Enter from 3 to 10 custom points to link level and volume values.
●
The
fi
rst custom point must be the lowest
fl
uid level in the vessel. Each successive point must
be greater than the preceding point.
●
The last point must be equal to or greater than the highest
fl
uid level in the vessel.
●
A custom point should be located at all transition points in the vessel shape (for example, at
custom point #9, where the shape changes from a cylinder to a cone).
●
The more complex sections should be de
fi
ned with more points.
NOTE
: The conical section of the illustration has been de
fi
ned by custom points 1 through 9.
●
Simpler sections require fewer de
fi
ning points.
NOTE
: A cylinder requires only custom points 9 and 10.
Custom Measurements