SDM 081
S-DIAS SAFETY DIGITAL MIXED MODULE
Page 12
07.02.2022
Mixed Module
Safety Parameters
Safety Levels
SDM 081
including
SCP
211/SCP 111-S
CPU
Module
Inputs
1-channel application:
PFH
D
= 2.3E-09 (1/h)
MTTF
D
= 1162 years
DC = 97 %
SFF = 99 %
PFH
D
= 7.7E-10 (1/h)
MTTF
D
= 1267 years
DC = 98 %
SFF = 99 %
1-channel application:
PL d
(1)
/ Cat. 2
SIL 3
2-channel application:
PL e / Cat. 4
SIL 3
Outputs
PFH
D
= 3.1E-09 (1/h)
MTTF
D
= 903 years
DC = 98 %
SFF = 99 %
PL e / Cat. 4
SIL 3
(1)
According to Table 5 and the corresponding notes EN / ISO 13849 in the "high" range.
In combination with the high MTTF
D
value and the good PFH
D
value, DC is the performance
level PLd according to table K.1.
Reason for SIL 3 with single-channel use:
Because the high SFF value is greater than 99 %, SIL 3 can be accepted with a hardware
tolerance (HFT) of 0 according to EN 62061.