S-DIAS SAFETY DIGITAL MIXED MODULE
SDM 081
07.02.2022
Page 23
5.1
Status LEDs
Bus Status
green
ON
bus communication OK
OFF
no supply available
BLINKING (5 Hz)
no communication
Safety Used
yellow
ON
module is used and no errors exist
OFF
module is not used or not in operational mode
Input Status
green
ON
input ON
OFF
input OFF
Output Status
yellow
ON
output on
OFF
output off
DC OK
green
ON
voltage is supplied to the output group
5.2
Applicable Connectors
Connectors:
X1-X5:
Connectors with spring terminals (included in delivery)
The spring terminals are suitable connecting ultrasonically compacted (ultrasonically welded)
strands.
Connections:
Stripping length/Sleeve length:
10 mm
Plug-in direction:
parallel to conductor axis or to PCB
Conductor cross section, rigid:
0.2-1.5 mm
2
Conductor cross section, flexible:
0.2-1.5 mm
2
Conductor cross section, ultrasonically compacted:
0.2-1.5 mm
2
Conductor cross section AWG/kcmil:
24-16
Conductor cross section flexible, with ferrule without plastic
sleeve:
0.25-1.5 mm
2
Conductor cross section flexible, with ferrule with plastic sleeve:
0.25-0.75 mm
2
(ground for reducing d2 of the
ferrule)
Содержание SDM 081
Страница 21: ...S DIAS SAFETY DIGITAL MIXED MODULE SDM 081 07 02 2022 Page 19...
Страница 23: ...S DIAS SAFETY DIGITAL MIXED MODULE SDM 081 07 02 2022 Page 21 4 Mechanical Dimensions...
Страница 27: ...S DIAS SAFETY DIGITAL MIXED MODULE SDM 081 07 02 2022 Page 25 6 Wiring 6 1 Wiring Example...
Страница 35: ...S DIAS SAFETY DIGITAL MIXED MODULE SDM 081 07 02 2022 Page 33 9 3 Example...