ETT 775
BUILD-IN TOUCH TERMINAL
Page 28
15.07.2020
11 Status and Error Messages
Status and error messages are displayed in the LASAL CLASS software status test.
POINTER or CHKSUM messages are shown on the terminal screen.
Number
Message
Definition
Cause/solution
00
RUN RAM
The user program is currently running in
RAM.
The display is not affected.
Info
01
RUN ROM
The user program stored in the program
memory module was loaded into the
RAM and is currently running.
The display is not affected.
Info
02
RUNTIME
The total time for all cyclic objects
exceeds the maximum time; the time can
be configured using 2 system variables:
-
Runtime: Remaining time
-
SWRuntime: Preset value for runtime
counter
Solution:
-
Optimize the application's
cyclic task.
-
Use higher capacity CPU.
-
Configure preset value
03
POINTER
Incorrect program pointers were detect-
ed before running the user program
Possible Causes:
-
The program memory module
is missing, not programmed or
defective.
-
The program in the user pro-
gram memory (RAM) is not
executable.
-
The buffer battery has failed.
-
The user program has overwrit-
ten a software error.
Solution:
-
Reprogram the memory mod-
ule, if the error reoccurs ex-
change the module.
-
Exchange the buffering battery
-
Correct programming error
04
CHKSUM
An invalid checksum was detected
before running the user program.
Cause/solution: s. POINTER
Содержание ETT 775
Страница 10: ...ETT 775 BUILD IN TOUCH TERMINAL Page 8 15 07 2020 2 Mechanical Dimensions...
Страница 19: ...BUILD IN TOUCH TERMINAL ETT 775 15 07 2020 Page 17 A mounting position of 60 120 is also required...
Страница 26: ...ETT 775 BUILD IN TOUCH TERMINAL Page 24 15 07 2020 7 6 2 2 PASSIVE...
Страница 29: ...BUILD IN TOUCH TERMINAL ETT 775 15 07 2020 Page 27 10 Process Diagram...