Page 31
27
OP PROG
The operating system is currently being
reprogrammed.
Info
28
OP INSTALLED
The operating system has been rein-
stalled.
Info
29
OS TOO LONG
The operating system cannot be loaded;
too little memory.
Restart, report error to
SIGMATEK.
30
NO OPERATING
SYSTEM
Boot loader message.
No operating system found in RAM.
Restart, report error to
SIGMATEK.
31
SEARCH FOR OS
The boot loader is searching for the
operating system in RAM.
Restart, report error to
SIGMATEK.
32
NO DEVICE
Reserved
33
UNUSED CODE
Reserved
34
MEM ERROR
The operating system loaded does not
match the hardware configuration.
Solution:
-
Use the correct operating
system version
35
MAX IO
Reserved
36
MODULE
LOAD
ERROR
The LASAL Module or project cannot be
loaded.
Solution:
-
Recompile and download the
entire project
37
BOOTIMAGE
FAIL-
URE
A general error has occurred while
loading the operating system.
Contact SIGMATEK
38
APPLMEM ERROR
An error has occurred in the application
memory (user heap).
Solution:
-
Correct allocated memory
access error
39
OFFLINE
This error does not occur in the control.
This error code is used in the
programming system to show
that there is no connection to the
control.
40
APPL LOAD
Reserved
41
APPL SAVE
Reserved
44
VARAN MANAGER
ERROR
An error number was entered in the
VARAN manager and stopped the
program.
Solution:
-
Read LogFile
45
VARAN ERROR
A required VARAN client was discon-
nected or a communication error has
occurred.
Solution:
-
Read LogFile
-
Error Tree
Содержание ETT 775
Страница 10: ...ETT 775 BUILD IN TOUCH TERMINAL Page 8 15 07 2020 2 Mechanical Dimensions...
Страница 19: ...BUILD IN TOUCH TERMINAL ETT 775 15 07 2020 Page 17 A mounting position of 60 120 is also required...
Страница 26: ...ETT 775 BUILD IN TOUCH TERMINAL Page 24 15 07 2020 7 6 2 2 PASSIVE...
Страница 29: ...BUILD IN TOUCH TERMINAL ETT 775 15 07 2020 Page 27 10 Process Diagram...