Address
Parameter
Description
2) if pass word lock is absent & if this
location is read it will return one.
3 )if password lock is present & to disable
this lock first send valid password to this
location then write “0000” to this location.
40027
Sim_Output A
This address is used to
simulate output1.
Analog Output 1 can be set to 10% by
writing a value1000 and can be set to 100%
by writing a
value 10000.
Note:
first
transducers simulation mode is
to be enable using address 40003.
This address is used to
simulate
Output 2.
Analog
Output 2 can be set to 10% by
writing a value1000 and can be set to 100%
by writing a value 10000.
Note:
first
transducers simulation mode is
to be enable
using address 40003.
40029
Sim_Output B
40031
Analog O/P
Type 1
This address is used to set the output
1 type as Voltage or Current.
Voltage = 1.
Current = 2.
40033
Output para
Select
This address is used to set the
Transducer type as
1)
Active Power = 1.
2)
Apparent Power = 2.
3)
Reactive power = 3.
4)
PF = 4.
5)
Phase Angle = 5.
57