56
This address allows the user to read and
write CT Primary value.The maximum
settable value is 9999 & also depends on
the per phase 1000 MVA Restriction of
power combined with PT primary.
40011
CT Primary
400 3
1
CT Secondary This address is used to read and write
the CT secondary value in range
between 1A to 5A.
40015
Device Address This address is used to set the Device
Address between 1 to 247.
This address is used to set the Baud
rate, Parity, No of Stop bits.
40017
RS 485 Setup
40019
Password
This address is used to set & reset the
password. Valid Range of Password can
be set is 0000 - 9999 .
1) if password lock is present & if this
location is read it will return zero.
Address
Parameter
Description
4) Single Phase = 1.
5) 3 Phase 4 wire balanced = 8.
6) 3 Phase 3 wire balanced = 2.
This address allows the user to read and
write PT Primary value. The PT Primary
value can be set between100 to 692.8
KVLL and also depends upon the per
phase 1000 MVA Restriction of power
combined with CT Primary.
40007
PT Primary
40009
PT Secondary This address is used to read and write
the PT secondary value
in range between 100V to 500V L-L.