Factory Chimney Top vent installation
Required installation components:
Chimney cap
Insulated chimney
Storm collar
Roof flashing
Ceiling support box or joist shield/fire stop spacer
Chimney connector pipe
Chimney connector adapter
Chimney connector
The chimney connector is a single or walled pipe used to con-
nect the stove to the chimney. For use with the SIERRA FLAME
wood-burning stoves the chimney connector MUST be 6” in
diameter, with a minimum thickness of 24 gauge black steel or 26
gauge blued steel
Aluminum and galvanized steel pipe is not acceptable for use
with the SIERRA FLAME wood-burning stove. These materials
cannot withstand the extreme temperatures of a wood fire and
can give off toxic fumes when heated.
DO NOT USE THE CONNECTOR PIPE AS A CHIMNEY
Each chimney connector or stove pipe section must be connected to the
stove flue collar and to each other with the male (crimped) end toward the
stove. Each adjacent piece of connector must be fastened with 2 screws.
This prevents any condensed or liquid creosote from running down the out-
side of the pipe or the stove top. All joints, including the flue collar connection
must be secured with three sheet metal screws to ensure that the sections
do not separate. For the best performance the chimney connector should be
as short and direct as possible, with no more than one 90 degree elbow. The
maximum horizontal run is 36” and a recommended total length of connector
pipe should not exceed 10 feet. Always slope horizontal runs upward ¼” per
foot toward the chimney. No part of the chimney connector may pass through
an attic or roof space, closet or other concealed-space, or through a floor ceiling. All sections of
the chimney connectors must be accessible for cleaning. Where passage through a wall or parti-
tion of combustible construction is desired, the installation must conform with NFPA 211 or CAN/
CSA-B365.