![Siemens XC10 Series Скачать руководство пользователя страница 65](http://html.mh-extra.com/html/siemens/xc10-series/xc10-series_installation-commissioning-maintenance_1265620065.webp)
Maintenance
65
Building Technologies
A6V10257473_b_en_--.doc
Fire Safety & Security Products
01.2010
14.2 Detailed fault display
Press simultaneously keys “1” and “3” of the
numeric keypad:
Faults appear for 5 seconds according to the table below
OL: Open Line
SC: Short Circuit
LED
N°
Color
Designation
State
Significance
Fixed
Multi-sector function: individual module (XCA1030) disconnected
2
Yellow
Fault
Slow
Multi-sector function: RS485 bus (OL / SC / communication fault)
Fixed
Multi-sector function: loss of agent
3
Yellow
Power supply fault
Slow
Multi-sector function: loss of agent (OL / SC)
5
Yellow
Earth fault
Fixed
Multi-sector function: earth fault
Fixed
Multi-sector function: actuator (OL / SC)
Slow
Multi-sector function: inter-blocking (OL / SC)
6
Yellow
Disable
Fast
Multi-sector function: ac inter-blocking (OL / SC)
Fixed
Multi-sector function: selector valve (SC)
Slow
Multi-sector function: selector valve (OL)
7
Yellow
Test
Fast
Multi-sector function: selector valve (incorrect status)
8
Red
Fire alarm
Fixed
Multi-sector function: actuator blocked
9
Red
Remote transmission
Fixed
Multi-sector function: power supply fault
Fixed
SC
11
Yellow
Mechanical blocked
Slow
OL
Monitored input 1
Fixed
SC
12
Yellow
Incorrect status
Slow
OL
Monitored input 2
Fixed
SC
Slow
OL
13
Yellow
Loss of agent
Fast
Incorrect status
Monitored input 3
Fixed
SC
14
Yellow
Manual blocked
Slow
OL
Monitored input 4
15
Yellow
Not used
Fixed
24 V output fuse blown
16
Yellow
Automatic blocked
Fixed
Key enabled more than 5 mn
Fixed
SC
19
Yellow
Sounders
Slow
OL
Monitored output 1