Overview
16
Building Technologies
A6V10257473_b_en_--.doc
Fire Safety & Security Products
01.2010
4.5
XCM1002
X
3
X
4
X
2
8
X
1
3
X
1
8
X
2
6
Fig. 5
XCM1002 board
Setting elements
X3
Internal buzzer Enable/Disable
Jumper up
(factory setting) : buzzer enabled
Jumper down : buzzer disabled (only for servicing)
X4
Type of power supply
Jumper up (factory setting) : FCP1004-E
Jumper down : do not use (for further use of external power supply)
X8
Operating access Level 2
Jumper on the right (factory setting) : Level 2 access using code
Jumper on the left : Level 2 access permanent
X13
Relay contact type 1
(NO or NC)
Jumper up : NC contact
Jumper down (factory setting) : NO contact
X14
Relay contact type 5
(NO or NC)
Jumper on the right : NC contact
Jumper on the left (factory setting) : NO contact
X15
Relay contact type 4
(NO or NC)
Jumper on the right : NC contact
Jumper on the left (factory setting) : NO contact
X16
Relay contact type 3
(NO or NC)
Jumper on the right : NC contact
Jumper on the left (factory setting) : NO contact
X17
Relay contact type 2
(NO or NC)
Jumper on the right : NC contact
Jumper on the left (factory setting) : NO contact
Other elements
F1 / F2
Pluggable fuse 2 AF
Fuse for protection of control outputs 4 (F1) and 5 (F2)
F3
Pluggable fuse 1 AF
Fuse for protection of 24V output
F4 / F5 / F6
Pluggable fuse 1 AT
Fuse for protection of control outputs 1 (F4), 2 (F5) and 3 (F6)
S1
Reset
—
S18-1 / S18-2
Not used
Do not change (factory setting : OFF)