Overview
17
Building Technologies
A6V10257473_b_en_--.doc
Fire Safety & Security Products
01.2010
PCB terminal blocks
1-2 (–) / 5-6 (+) 24V power supply
X1
Plug-in block 6 points
(1.5 mm
2
max.)
3-4 (+)
Power supply monitoring
1 (+) / 2 (–)
Monitored output 5
X5
Plug-in block 4 points
(2.5 mm
2
max.)
3 (+) / 4 (–)
24V use output
1 (+) / 2 (–)
Monitored output 3 (control polarities, reversed in standby)
X6
Plug-in block 4 points
(2.5 mm
2
max.)
3 (+) / 4 (–)
Monitored output 4
1 (+) / 2 (–)
Monitored output 1 (control polarities, reversed in standby)
X7
Plug-in block 4 points
(2.5 mm
2
max.)
3 (+) / 4 (–)
Monitored output 2 (control polarities, reversed in standby)
1 (+) / 2 (–)
Monitored input 1
3 (+) / 4 (–)
Monitored input 2
5 (+) / 6 (–)
Monitored input 3
X9
Plug-in block 8 points
(1.5 mm
2
max.)
7 (+) / 8 (–)
Monitored input 4
1 (+) / 2 (–)
Fire detectors zone 1
3 (+) / 4 (–)
Fire detectors zone 2
5 (+) / 6 (–)
Fire detectors zone 3
X10
Plug-in block 8 points
(1.5 mm
2
max.)
7 (+) / 8 (–)
Extinguishing manual control
1 / 2
Potential-free contact relay 1 (NO or NC)
3 / 4
Potential-free contact relay 2 (NO or NC)
5 / 6
Potential-free contact relay 3 (NO or NC)
7 / 8
Potential-free contact relay 4 (NO or NC)
X11
Plug-in block 10 points
(1.5 mm
2
max.)
9 / 10
Potential-free contact relay 5 (NO or NC)
1 … 8 (–)
Logical outputs 1 to 8
X12
Plug-in block 10 points
(1.5 mm
2
max.)
9 / 10
Not used
X21
Jack 2.5 mm
—
Maintenance PC
1 (+)
Reset
X27
Plug-in block 4 points
(1.5 mm
2
max.)
2 … 4 (+)
Unmonitored inputs 2 to 4
X28
Faston 5.3 mm
(+)
To positive of battery (to provide “Total loss of power supply”
function (see note 1)
X30 (*)
Flat cable 26 points
—
Connection for multi-sector module XCA1030
X35
Terminal 12 points
—
Connection for 4 digits display
X18, 23, 24,
26
Not used
—
—
(*) on welding side
Note 1: The XC10 provides the EN54-2 option with requirement 8.4 called “Total loss of power”. This option when selected activates the
system fault LED and the buzzer continuously, for at least 1 hour after a low discharge battery disconnection. The option can be
selected by wiring the +BAT terminal to the positive voltage of batteries (use of remaining power after battery disconnection).