Programming
55
Building Technologies
A6V10257473_b_en_--.doc
Fire Safety & Security Products
01.2010
12.7 Steps 15 to 19 - Relay contact 1 to 5
Step
Option
Description
Relay output 1 : select the function
01
Processing as “Fire control A”
02
Processing as “Fire control B”
03
Processing as “Fire control C”
04
Active in state ”Fire alarm”
05
Active in state ”Activated”
06
Active in state ”Released”
07
Active in state “Fire alarm” or “Activated” or ”Released”
08
Active in state “Activated” or ”Released”
09
Active in state “Loss of agent”
10
Active in state “Detector test”
11
Active in state “Disabled”
12
Active in state “Emergency hold/abort”
13
Active in state “Mechanical blocked”
14
Active in state “Automatic blocked”
15
Active in state “Manual blocked”
16
Active in state “Automatic blocked” or “Manual blocked”
17
Active in state “Automatic blocked” and “Manual blocked”
18
Processing as "RT-alarm"
19
Processing as "RT-fault"
20
Inactive in state “Fault” or “Disable” or “Mechanical blocked” or “Loss of agent” or “Incorrect status”
Active in all other states
21
Active during 5 seconds when the key reset is pressed
Application: reset of an XC10 panel and reset of an ASD system within a single operation
15
22
Active in state:
- “Manual blocked”
- Zone 4 in fault condition
- “Processing as actuator” control lines in fault condition
- Actuator disabled
Relay contact 2 : select the function
16
Same options as relay contact 1 – default = 01
Relay contact 3 : select the function
17
01
Processing as "RT-fault"
Relay contact 4 : select the function
18
Same options as relay contact 1 – default = 12
Relay contact 5 : select the function
19
Same options as relay contact 1 – default = 16