Above ground conduit and wiring
1. Disassemble the Flexa system
Remove the end, flex adapter by pushing in the ring of the
conduit fitting, and pulling out the conduit.
2. Fit Flexa adapter into enclosure box
Attach the top flex adapter into the hole inside the service hatch
with the washer on the outside of the box, and secure inside
with the locking ring.
Push in ring
Pull out conduit
3. Attach Flexa conduit
Feed the Flexa conduit (not supplied) from the rear left of the
unit and press fit into the flex adapter. Use the slots in the rear
channel to cable tie the conduit in place if necessary.
4. Feed through wiring
Pull the wires from the service disconnect into the switchgear
area running at least 12” (300mm) of wiring into the interior.
Connect the wires to the terminal block according to the wiring
diagram inside the service hatch. Also see section Wire and
Commission in this document.
CAUTION
To achieve the NEMA 3R rating, the conduit must be fitted
correctly into the supplied fitting.
Check that the conduit is pressed firmly into the flex adapters,
and the locking ring is secure.
415V 3PH
Copper Conductors Only
N
x
VersiCharge Ultra 50™ |
Installation Manual
22