APPENDIX D– Hardwire Bending Diagram
Dedicated 2 Pole 50/60 amp
commom trip branch
circuit breaker
VersiCharge Hardwired Models
NOTE:
The rating of the circuit breaker that will be required is based on the ampere rating of the EVSE; 40A requires 50A breaker,
48A requires 60A breaker. Also, the wiring should not be exposed to weather/water or conditions that could potentially damage
wiring or cause a short.