6 – 9
6.7
Reclosing a circuit breaker tripped by the trip unit
NOTE
The reason for tripping can be displayed using the "QUERY" button on the trip unit. This is stored for at least two days, provided that the
trip unit was activated for at least 10 minutes before tripping.
1
Find reason for
tripping
2
Indicator
Overload in
main conductor
Overload in neutral
conductor
Short circuit:
short-time-delay trip
Short circuit:
instantaneous trip
Ground fault trip
3
Find and rem-
edy cause
- Check downstream load
- Check
trip unit
settings
- Inspect switchgear
- Check downstream load
4
Inspect circuit
breaker
Inspect contact system for possible damage
5
Clear trip cause
Содержание UL 1066
Страница 43: ...6 12 7 Reset reclosing lockout 8 Charge closing spring 9 Switch ON Frame size II Frame size III 9X ...
Страница 56: ...7 5 7 2 Frame size II fused ...
Страница 58: ...7 7 ...
Страница 63: ...7 12 8 27 210 0 8 27 210 0 8 27 210 0 3 75 95 2 ...
Страница 64: ...7 13 ...
Страница 65: ...7 14 7 7 Frame size III fuse carriage ...
Страница 66: ...7 15 ...
Страница 69: ...7 18 7 9 External sensor for neutral conductor WLNCT2 ...
Страница 70: ...7 19 WLNCT3 ...
Страница 85: ...9 5 I tripping Ground fault tripping ...
Страница 231: ...15 12 Pre assembling the locking module Installing 0767 1 2 3 4 6 5 ...
Страница 232: ...15 13 1 Socket head cap screw M5 with washer and nut 7 8 Size 4 5 Nm 45 lb in ...
Страница 271: ...19 10 Function check Then Fit back front panel and side cover on the right if it was removed page 23 4 10 ...
Страница 280: ...21 2 Installing the door sealing frame Not for use with fuse carriages Catalog No Door sealing frame WLDSF 1 2 3 NOTICE ...
Страница 289: ...23 7 23 3 3 Installing arc chutes 1 2 6 5 PH 2 0043 02 3 4 5 6 For frame size III 3 PH 2 ...
Страница 298: ...23 16 6 7 8 9 5 2 1 Size 5 mm ...
Страница 333: ......