9 – 81
Setting principle
Indicators
Module test
The correct operation of the
c
modules can be verified in the test mode. The test mode is started by pushing the "TEST" button
once. All outputs and the associated LEDs are switched off. The color of the DEVICE LED changes from green to yellow.
Testing inputs and outputs
Pushing the "TEST" button several times in quick succession when an LED is on switches the respective input/output on and off alternately.
LED
Indication
Significance
DEVICE
green
Module in operation
yellow
Module in test mode
red
Module faulty
c
green
Connection to
c
available
off
No connection to
c
All other LEDs
yellow
Option set or signal available
off
Option not set or no signal available
NOTICE
Unintended operation of the circuit breaker and other devices.
The test circuits of this unit emit real output signals that may cause operation of the circuit breaker and other devices that
may be connected to the associated
c
module.
During the test, the circuit breaker and downstream devices shoud be isolated to prevent unintended device operations.
Pressing the
"
TEST
"
Button
Reaction
Twice quickly
- LED 1 on
- Input/output 1 on
After a pause,
twice quickly
- LED 1 and input/output 1 off, LED 2 on
- Input/output 2 on
After a pause,
twice quickly
- LED 2 and input/output 2 off, LED 3 on
- Input/output 3 on
...
...
After a pause,
twice quickly
- LED 5 and input/output 5 off, LED 6 on
- Input/output 6 on
After a pause, once
Input/output 6 off, all LEDs on
Once
Test mode starts again, all inputs/outputs and the associated LEDs are off
The value 0.1 is set if the
rotary coding switch is positioned
3 x 0.5
1/8“
in this
segment
Содержание UL 1066
Страница 43: ...6 12 7 Reset reclosing lockout 8 Charge closing spring 9 Switch ON Frame size II Frame size III 9X ...
Страница 56: ...7 5 7 2 Frame size II fused ...
Страница 58: ...7 7 ...
Страница 63: ...7 12 8 27 210 0 8 27 210 0 8 27 210 0 3 75 95 2 ...
Страница 64: ...7 13 ...
Страница 65: ...7 14 7 7 Frame size III fuse carriage ...
Страница 66: ...7 15 ...
Страница 69: ...7 18 7 9 External sensor for neutral conductor WLNCT2 ...
Страница 70: ...7 19 WLNCT3 ...
Страница 85: ...9 5 I tripping Ground fault tripping ...
Страница 231: ...15 12 Pre assembling the locking module Installing 0767 1 2 3 4 6 5 ...
Страница 232: ...15 13 1 Socket head cap screw M5 with washer and nut 7 8 Size 4 5 Nm 45 lb in ...
Страница 271: ...19 10 Function check Then Fit back front panel and side cover on the right if it was removed page 23 4 10 ...
Страница 280: ...21 2 Installing the door sealing frame Not for use with fuse carriages Catalog No Door sealing frame WLDSF 1 2 3 NOTICE ...
Страница 289: ...23 7 23 3 3 Installing arc chutes 1 2 6 5 PH 2 0043 02 3 4 5 6 For frame size III 3 PH 2 ...
Страница 298: ...23 16 6 7 8 9 5 2 1 Size 5 mm ...
Страница 333: ......