Dry Contact Leads

Power Leads

Blue

Grey

Connecting Optional Form C Dry Contact & Audible Alarm
(“D” suffix near end of model number)

Three  (3)  3’  (~1m)  18  AWG  wires  are  included  through  the 
nipple  with  this  option.  (These  are  smaller  than  the  10  AWG 
SPD conductors.) Gray is Common, Blue is Normally Open and 
Red  is  Normally  Closed.  Normally  Open  and  Normally  Closed 
are based on the ‘Normal’ condition of the unit being energized 
and operating correctly. When not energized, or not operating 
correctly,  the  contacts’  state  will  be  opposite  of  ‘Normal’.  (We 
generally recommend the Normally Closed configuration because 
it  detects  disconnected  or  failed  wiring  whereas  Normally 
Open does not.) The contact is rated 250V, 5A. Higher energy 
applications require supplemental relaying. This option monitors 
suppression  element  condition  and  is  not  intended  for  use  as 
phase loss or phase detection monitoring. If the Dry Contacts are 
not utilized, insulate lead ends, coil and secure. Audible Alarm 
will still function correctly.

Remote Indication Option

This is a supplemental diagnostic LED that can be mounted in a 
conspicuous location if the SPD is installed such that on-board 
LEDs are not readily visible. A green LED bezel assembly includes 
two  pre-attached  wires  and  two  butt-splice  connectors.  The 
SPD includes two yellow 18 AWG wires, pre-wired through the 
SPD’s nipple mounting connection. Pre-plan the installation per 
normal installation Instructions. Mount the LED assembly in an 
appropriate conspicuous location. Connect the LED wires to the 
yellow SPD wires with the provided butt-splice connectors. These 
are not polarity sensitive. Test by energizing and de-energizing 
SPD. Operation is straightforward: green LED On = SPD is OK. If 
the LED is out, the SPD has failed, power is not present, or one of 
more phases are not energized. 

Figure 6: Dry Contact

• 

Normally Closed (suggested):    
Use Gray and Blue

• 

Normally Open:  

 

Use Gray and Red

Blue

Normally Closed

Gray

Common

Red

Normally Opened

Normal Operation

Green LED Indicators

Each phase’s LED Indicator illuminates when the SPD is energized 
and operating correctly. Every suppression element is monitored 
and  connected  by  logic  to  the  LED.  Should  any  suppression 
element fail, the green LED will extinguish.

Form C Dry Contact and Audible Alarm Option

Similar  to  the  Green  LEDs  above,  the  dry  contact  will  change 
state and the audible alarm will sound upon suppression element 
failure. The audible alarm may be silenced by removing power 
to the SPD.

4

Содержание TPS3 09 Series

Страница 1: ...UL 1449 4th Edition SPD usa siemens com spd TPS3 09 User Manual USA ...

Страница 2: ...age rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance wit...

Страница 3: ...need for supplemental overcurrent protection Type 1 SPDs include internal overcurrent protection As a generalization it is more practical to install SPDs on the load side of the main overcurrent protection device for maintenance and serviceability reasons When connected on load side of main disconnect we suggest connecting via a 30A circuit breaker due to 10 AWG conductors The circuit breaker serv...

Страница 4: ...ded systems are inherently unstable and can produce excessively high line to ground voltages during certain fault conditions During these fault conditions any electrical equipment including an SPD may be subjected to voltages which exceed their designed ratings This information is being provided to the user so that an informed decision can be made before installing any electrical equipment on an u...

Страница 5: ...deenergized 5 Identify breaker location and SPD location Position SPD such that LEDs are best visible 6 Mount SPD weather resistant applications require additional sealing o rings etc not included Remove an appropriately sized knockout from panel Connect conductors as appropriate short and straight as possible Hi Legs are Phase B 7 Label or mark conductors as appropriate neutral white ground green...

Страница 6: ...uch that on board LEDs are not readily visible A green LED bezel assembly includes two pre attached wires and two butt splice connectors The SPD includes two yellow 18 AWG wires pre wired through the SPD s nipple mounting connection Pre plan the installation per normal installation Instructions Mount the LED assembly in an appropriate conspicuous location Connect the LED wires to the yellow SPD wi...

Страница 7: ...duct Returnedproducts mustbesenttothefactorywiththetransportationchargesprepaid In addition the company also warranties unlimited replacement of modular and component parts within the warranty period previously described Thecompanyspecificallydisclaimsallotherwarranties expressed or implied Additionally the company is not be responsible for incidental or consequential damages resulting from any de...

Страница 8: ...tion provided in this manual contains merely general descriptions of characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the product An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract All product designations may be trademarks or produ...

Отзывы: