Voltage Rating & Application

Before installing SPD, verify the nameplate voltage has the same 
voltage rating as the power distribution system. If unsure, call 
Siemens TPS Tech Support at 1.888.333.3545 before proceeding. 
The SPDs specifier or user should be familiar with the configuration 
and arrangement of the power distribution system. The system 
is  defined  by  how  the  secondary  windings  of  the  transformer 
supplying the service entrance main or load are configured. This 
includes whether or not the transformer windings are referenced 
to earth via a grounding conductor. The system configuration is 
not based on how any specific load or equipment is connected to 
a particular power distribution system. SPDs should be installed 
per  the  distribution  system,  not  per  a  load  or  motor’s  wiring 
connection. 

For example, suppose a 480V three phase motor appears to be 
connected as a 480V Delta. In actuality, the serving distribution 
system might be a 480Y/277V grounded Wye, with or without a 
neutral pulled to the motor or MCC. The system is still a 480Y/277V 
Wye, even though the load is connected as a Delta. A grounded 
Wye has a defined reference to ground (i.e., neutral is bonded to 
ground). In contrast, some Delta systems are ungrounded, which 
have no reference to ground. 

Table 3: Model Number Decoder

Model

Voltage Code

Service Voltage

TPS3A09

A

240/120V 1Ø, 3W Plus 
Ground,

TPS3B09

B

240/120V 3Ø, 4W Plus 
Ground High Leg Delta 

TPS3C09

C

208Y/120V 3Ø, 4W Plus 
Ground

TPS3D09

D

240V 3Ø, 3W Plus Ground 

TPS3E09

E

480Y/277V 3Ø, 4W Plus 
Ground

TPS3F09

F

480V 3Ø, 3W Plus Ground 

TPS3G09

G

600V 3Ø, 3W Plus Ground 

TPS3K09

K

380Y/220V 3Ø, 4W Plus 
Ground 

TPS3L09

L

600Y/347V 3Ø, 4W Plus 
Ground 

TPS3S09

S

400Y/230V 3Ø, 4W Plus 
Ground 

SPDs on Ungrounded Systems

Caution – 

Ungrounded systems are inherently unstable and can 

produce excessively high line-to-ground voltages during certain 
fault  conditions.  During  these  fault  conditions,  any  electrical 
equipment  including  an  SPD,  may  be  subjected  to  voltages 
which exceed their designed ratings. This information is being 
provided to the user so that an informed decision can be made 
before  installing  any  electrical  equipment  on  an  ungrounded 
power system.

Parts List and Inspection

Items included in the package consist of the following:
• 

1 TPS3 09 SPD including 3’ (1~m) conductors

• 

1 User’s Manual (this document)

*See figure 4 for installation

If the Flush Mount Kit was ordered, additional parts are supplied 
as follows:
• 

1 Flush Mount Plate

• 

4 Mounting Screws

TPS3 09 has demonstrated 200kA or 100kA Short Circuit Current 
Ratings (SCCR) including leads. See UL Label markings on SPD or 
see Data Sheet for specs.) Supplemental overcurrent protection 
is  not  required  to  protect  this  SPD.  However,  NEC®  and  CEC 
convention requires that connecting conductors have overcurrent 
protection in Type 2 applications. Follow applicable codes.

This  device  features  internal  overcurrent  and  overtemperature 
protection  that  will  disconnect  affected  surge  suppression 
components at the end of their useful life, but will maintain power 
to  the  load  –  now  unprotected.  If  this  situation  is  undesirable 
for  the  application,  follow  these  instructions  for  replacing  the 
device. TPS3 09 is ultrasonically welded closed and contains no 
user serviceable parts.

Table 2: Specifications 

Specifications

Temperature Operating

-40

o

C (-40

o

F) to 60

o

C (+140

o

F)

Temperature Storage

-55

o

C (-67

o

F) to 65

o

C (+149

o

F)

Wire Size & Installation
Torque

10 AWG; 18 inch-pounds

Appropriate Circuit Breaker
based on conductor size

30A (SPD includes internal OCP)

NEMA 250 Enclosure Rating

Type 4X with appropriate 
sealing & sealing condulets

3.00

(76.20)

0.19

(4.83)

8.28

(210.31)

3.67

(93.22)

2.21

(56.13)

7.41

(188.21)

Weight: 3lbs (1.4kg)

Figure 2: Dimensions & Weight

2

Содержание TPS3 09 Series

Страница 1: ...UL 1449 4th Edition SPD usa siemens com spd TPS3 09 User Manual USA ...

Страница 2: ...age rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance wit...

Страница 3: ...need for supplemental overcurrent protection Type 1 SPDs include internal overcurrent protection As a generalization it is more practical to install SPDs on the load side of the main overcurrent protection device for maintenance and serviceability reasons When connected on load side of main disconnect we suggest connecting via a 30A circuit breaker due to 10 AWG conductors The circuit breaker serv...

Страница 4: ...ded systems are inherently unstable and can produce excessively high line to ground voltages during certain fault conditions During these fault conditions any electrical equipment including an SPD may be subjected to voltages which exceed their designed ratings This information is being provided to the user so that an informed decision can be made before installing any electrical equipment on an u...

Страница 5: ...deenergized 5 Identify breaker location and SPD location Position SPD such that LEDs are best visible 6 Mount SPD weather resistant applications require additional sealing o rings etc not included Remove an appropriately sized knockout from panel Connect conductors as appropriate short and straight as possible Hi Legs are Phase B 7 Label or mark conductors as appropriate neutral white ground green...

Страница 6: ...uch that on board LEDs are not readily visible A green LED bezel assembly includes two pre attached wires and two butt splice connectors The SPD includes two yellow 18 AWG wires pre wired through the SPD s nipple mounting connection Pre plan the installation per normal installation Instructions Mount the LED assembly in an appropriate conspicuous location Connect the LED wires to the yellow SPD wi...

Страница 7: ...duct Returnedproducts mustbesenttothefactorywiththetransportationchargesprepaid In addition the company also warranties unlimited replacement of modular and component parts within the warranty period previously described Thecompanyspecificallydisclaimsallotherwarranties expressed or implied Additionally the company is not be responsible for incidental or consequential damages resulting from any de...

Страница 8: ...tion provided in this manual contains merely general descriptions of characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the product An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract All product designations may be trademarks or produ...

Отзывы: