TPS3 09 Installation Instructions

Pre-Plan your installation. You need to accomplish the 
following:

•  Meet all National and Local codes 

(NEC

®

 Article 285 and 

UL 1449 address SPDs).

•  Confirm System voltage to SPD voltage 

(120V SPD will 

fail instantly on 240V, 277V, etc.).

•  Mount SPD as close to panel or equipment as possible 

to keep leads short 

(long leads hurt performance 

substantially).

•  Ensure leads are as short and straight as possible, 

including neutral and ground. If using a breaker, use a 
breaker position that is close to the SPD and the panel’s 
neutral & ground.

•  If using a breaker, recommended breaker size is 30A 

due to 10 AWG conductor.

•  Make sure system is grounded per NEC

®

 and clear of 

faults before energizing SPD

 (inadvertent system problem 

may fail SPD). 

•  Never Hi-Pot test Any SPD

 (will prematurely fail SPD).

•  Do not install the TPS3 09 through the bottom of a 

NEMA 3R panel. Dripping water will prematurely fail the 
SPD  

(a sealed pipe nipple installed in the SPD may be a 
solution).

 

1.  Use voltmeter to check voltages and ensure correct SPD. 

See Data Sheet for specs & wire-outs.

2.  Determine Mounting location – weather resistant 

equipment may be required.

3.  If SPD has optional Dry Contact and Flush Mount Kit, 

pre-plan their installation. See Figures 4 & 6. (If flush 
mounting, be careful to not drop SPD into wall).

4.  Remove power from panel/source. Confirm panel/source is 

deenergized.

5.  Identify breaker location and SPD location. Position SPD 

such that LEDs are best visible.

6.  Mount SPD – weather resistant applications require 

additional sealing, o-rings, etc. (not included).

 

-

Remove an appropriately sized knockout from panel. 

 

-

Connect conductors as appropriate – short and straight as 
possible (Hi-Legs are Phase B).

7.  Label or mark conductors as appropriate (neutral: white, 

ground: green, energized: black, hi-leg: orange).

8.  Make sure system is bonded per NEC

®

 and is clear of 

hazards or faults before energizing (N-G bonding not per 
NEC

®

 will fail SPDs: #1 cause of SPD failures).

9.  Energize and confirm proper operation of green LED 

indicators and/or options.

A

B

C

G

N

BREAKER

•  Use closest breaker to SPD
•  Locate SPD close to 

intended breaker

•  Keep Leads Short as 

Possible

•  Avoid Sharp Bends

Figure 5: Lead Lengths

Leads: Short & Straight
Cut Excess; Do Not Coil or Loop

• 

Cut Off  
Excess Length

• 

Do Not Loop  
Or Coil

• 

Short & Straight

 

Not 
Good

 

Good

Figure 4: Typical Flush Mount Installation

 

SPD

Hex Standoff

(4 Provided)

Mounting Surface

Mounting Screws
(4 Places, Not Provided)

Flush Mount Kit Screws
(8 Provided)

Phase,Ground,

Neutral Wires

Flush Mount Plate

Removed Material

Hazardous voltage.
Will cause death or serious injury.

Keep Out.

Qualified personnel only.

Disconnect and lock off all power before 

working on this equipment.

DANGER

Figure 3:  Panel Installation  

To Protected Loads

CONDUCTING DIELECTRIC AND/OR 

HI-POTENTIAL TESTING WILL CAUSE

INTERNAL DAMAGE TO TPS3 UNIT.

Do not perform dielectric or high potential 

tests with the TPS3 unit installed.

NOTICE

3

Содержание TPS3 09 Series

Страница 1: ...UL 1449 4th Edition SPD usa siemens com spd TPS3 09 User Manual USA ...

Страница 2: ...age rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance wit...

Страница 3: ...need for supplemental overcurrent protection Type 1 SPDs include internal overcurrent protection As a generalization it is more practical to install SPDs on the load side of the main overcurrent protection device for maintenance and serviceability reasons When connected on load side of main disconnect we suggest connecting via a 30A circuit breaker due to 10 AWG conductors The circuit breaker serv...

Страница 4: ...ded systems are inherently unstable and can produce excessively high line to ground voltages during certain fault conditions During these fault conditions any electrical equipment including an SPD may be subjected to voltages which exceed their designed ratings This information is being provided to the user so that an informed decision can be made before installing any electrical equipment on an u...

Страница 5: ...deenergized 5 Identify breaker location and SPD location Position SPD such that LEDs are best visible 6 Mount SPD weather resistant applications require additional sealing o rings etc not included Remove an appropriately sized knockout from panel Connect conductors as appropriate short and straight as possible Hi Legs are Phase B 7 Label or mark conductors as appropriate neutral white ground green...

Страница 6: ...uch that on board LEDs are not readily visible A green LED bezel assembly includes two pre attached wires and two butt splice connectors The SPD includes two yellow 18 AWG wires pre wired through the SPD s nipple mounting connection Pre plan the installation per normal installation Instructions Mount the LED assembly in an appropriate conspicuous location Connect the LED wires to the yellow SPD wi...

Страница 7: ...duct Returnedproducts mustbesenttothefactorywiththetransportationchargesprepaid In addition the company also warranties unlimited replacement of modular and component parts within the warranty period previously described Thecompanyspecificallydisclaimsallotherwarranties expressed or implied Additionally the company is not be responsible for incidental or consequential damages resulting from any de...

Страница 8: ...tion provided in this manual contains merely general descriptions of characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the product An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract All product designations may be trademarks or produ...

Отзывы: