Building Technologies
- 14 -
TEL50.GSM
5.
Technical data
Power supply
10…30 VDC stabilized (10 -15% 50-60Hz with supplied power supply)
Average consumption
In operation: 700mA @ 12VDC
On stand-by: 60mA @ 12VDC
LED indicator lamps
- Power supply present
- GSM field present
- Status of alarm input
- Status of relay outputs (2)
Alarm input
Potential-free and normally open (factory setting) or normally closed (selectable)
Temperature sensor input
LG-Ni1000
Measuring range
-30°C … +60°C
Length of temp. sensor connections
50 m max with 1.5 mm
2
cable
Control outputs (2)
Potential-free contact relay 250V AC 3A
Protection rating
IP42 when correctly installed
Operating temperature
0…50°C
Operating humidity
20…90% R.H. without condensation
Dimensions
139 mm x 98 mm x 40 mm
compliant
Health and Safety (Art. 3.1 a)
EN60950:2000
EMC (Art. 3.1 b)
EN 301489-7 v1.1.1 (09/2000)
RF spectrum efficiency (Art. 3.2)
(3-2000) EN 301419-1 v4.1.1 incl. EN 301511 v7.0.1 (12/2000)