78 / 100
Siemens
Synco™ living Operating instructions
CE1B2707en
Building Technologies
Central apartment unit QAX910
23.08.2008
For each fault output, the following settings can be made:
Fault priority: The priority (urgent or Not urgent) with which the relay should be
energized can be selected here
Fault source: Defines whether the relay should respond only in the case of
internal faults or only in the case of external faults (faults transmitted via bus)
Maximum one bus fault status message can be handled. If both relays
are set as bus relays with different priorities, only one of them can be
energized at a time, even if several faults with different priorities are
pending on the bus! It is therefore recommended to configure only one
relay as a bus fault relay.
Fault relay
1
2
FS fault priority
All
All
Fault priority
Urgent
Not urgent
All
Urgent
Not urgent
All
FS fault source
Internal
Bus
Fault source
Internal
Bus
Internal
Bus
FS Factory
setting
The fault relay remains energized until the fault is acknowledged.
Texts
Plant name
Assign the plant or the apartment a self-explanatory name,
e.g. ”Main street 22“:
Main menu > Settings > Text > Plant name:
Room names 1 – 12
Assign the rooms self-explanatory names, e.g. Living, Eating, Parents, Chil-
dren, Bathroom, etc.:
Main menu > Settings > Text > Rooms > Room X:
Switching group names 1 – 8
Assign the switching groups self-explanatory names, e.g. Living, Eating, Par-
ents, Children, Bathroom, etc.
Main menu > Settings > Text > Switching groups > Switching group X:
Содержание Synco living
Страница 2: ......
Страница 97: ...97 100 Siemens Synco living Operating instructions CE1B2707en Building Technologies 23 08 2008 ...
Страница 98: ...98 100 Siemens Synco living Operating instructions CE1B2707en Building Technologies 23 08 2008 ...
Страница 99: ......