background image

Technical data 

SSD31.. 

SSD81.. 

SSD61.. 

AC 24 V or 

DC 24 V 

Power supply 

Operating voltage 
 Voltage 

tolerance 

AC 230 V 

± 15 % 

AC 24 V 

± 20 % 

± 20 % 

± 25 % 

Rated frequency 

50 / 60 Hz 

Max. power consumption 

6 VA 

0.8 VA 

2.5 VA 

 Fuse for incoming cable 

2 A, quickblow 

Control

Control 

signal

3-position

 

DC 0...10 V 

Input impedance for DC 0...10 V 

> 100 kOhm 

Positioning accuracy for DC 0...10 V 

< 2 % of nominal stroke

Parallel operation (number of actuators) 

1)

max. 6 

max. 24 

max. 10 

Functional data 

Run time for 5.5 mm stroke at 50 Hz 

150 s 

75 s 

Nominal stroke

5.5 mm

Nominal force 

> 250 N 

Perm. temperature of  

medium in the connected valve

1...110°C 

Electrical connections  Connecting cable of basic types 

1.5 m 3-core to EN 60320 / IEC 60227 

ASY 

99, 

ASY100

 cable 

diameter 

maximal wire cross section 

< 5 mm 

0.5 mm

2

 

< 5 mm 
0,5 mm

2

 

 Standards 

Meets requirements for CE marking: 
EMC directive 

2004/108/EC 

Immunity EN 

61000-6-2

Industrial

2)

 

Emission EN 

61000-6-3

Residential

Low 

voltage 

directive

2006/95/EC

Electrical safety EN 60730-1 

Protection class to EN 60730

 

II

 

III

 

Contamination level

 

EN 60730, Class 2

 

Housing protection 

Upright to horizontal 

IP40 to EN 60529 

UL approbation

 

UL 873

 

cUL approbation

 

C22.2 No. 24-93

 

Environmental compatibility 

ISO 14001 (Environment) 

ISO 9001 (Quality) 

SN 36350 (Environmentally compatible products) 

RL 2002/95/EG (RoHS) 

Dimensions / weight 

Dimensions 

refer to 

«Dimensions», page 8 

Coupling thread to valve 

union nut M30x1.5 mm 

Weight

0.35 kg

Housing colors 

Base and cover 

RAL 7035 light gray 

1)

Provided the controllers’ output is sufficient

2)

Transformer 160 VA (e.g. Siemens 4AM3842-4TN00-0EA0) for AC 24 V actuators

General ambient 
conditions 

Operation

 

EN 60721-3-3

 

Transport

 

EN 60721-3-2

 

Storage

 

EN 60721-3-1

 

Environmental conditions 

Class 3K3 

Class 2K3 

Class 1K3 

Temperature 

+1...+50 °C 

–25...+70 °C

–5...+50 °C

Humidity 

5...85 % r.h. 

< 95 % r.h. 

5...95 % r.h. 

Содержание SSD31 Series

Страница 1: ...38 78 Смоленск 4812 29 41 54 Сочи 862 225 72 31 Ставрополь 8652 20 65 13 Тверь 4822 63 31 35 Томск 3822 98 41 53 Тула 4872 74 02 29 Тюмень 3452 66 21 18 Ульяновск 8422 24 23 59 Уфа 347 229 48 12 Челябинск 351 202 03 61 Череповец 8202 49 02 64 Ярославль 4852 69 52 93 сайт www acvatix nt rt ru эл почта atv nt rt ru Electrical Actuators for Combi valve types VPI45 SSD31 SSD81 SSD61 SSD31 operating vo...

Страница 2: ...Y8L15 Connecting cable 1 5 m ASY8L25 Connecting cable 2 5 m ASY8L25B Connecting cable 2 5 m with Batigyr connector ASY8L45 Connecting cable 4 5 m ASY8L45HF Connecting cable 4 5 m halogen free VDE 0207 24 AC 24 V 3 position ASY98 Retaining screw for terminal block connectors ASY99 Terminal block connector for 3 position actuator SSD81 00 AC 24 V ASY100 Terminal block connector for DC 0 10 V modulat...

Страница 3: ...ent switch off in the event of overload and in stroke end positions Parallel operation of 6 SSD31 24 SSD81 and 10 SSD61 possible provided the controllers output is sufficient Terminal block connectors for custom made cables available only for use with AC 24 V and AC DC 24 V actuators Connecting cables with AC 24 V and AC 230 V connectors cannot be mixed up Halogen free cables available 4891Z19 Acc...

Страница 4: ... 00 the separately ordered terminal block connector and connecting cable must be fitted 90 4362Z01 90 When commissioning check wiring and the functioning of the actuator Actuator stem extends from position 0 to 1 Valve opens Actuator stem retracts from position 1 to 0 Valve closes During commissioning and whenever the operating voltage is switched on the SSD61 runs a self calibration routine Valve...

Страница 5: ...als The actuator must be commissioned only with a correctly mounted valve in place SSD actuators cannot be repaired the complete unit must be replaced Broken connecting cables can be replaced see Accessories page 2 Disposal The device must not be disposed of together with domestic waste This applies in particular to the PCB Legislation may demand special handling of certain components or it may be...

Страница 6: ...ts for CE marking EMC directive 2004 108 EC Immunity EN 61000 6 2 Industrial 2 Emission EN 61000 6 3 Residential Low voltage directive 2006 95 EC Electrical safety EN 60730 1 Protection class to EN 60730 II III Contamination level EN 60730 Class 2 Housing protection Upright to horizontal IP40 to EN 60529 UL approbation UL 873 cUL approbation C22 2 No 24 93 Environmental compatibility ISO 14001 Env...

Страница 7: ...864Z15 Control signal CLOSE Control signal OPEN System potential AC 24 V G0 Y G 4864Z16 System neutral Control signal DC 0 10 V System potential AC DC 24 V Connection diagrams N Controller Y Actuator L System potential AC 230 V N System neutral Y1 Y2 Control signal OPEN CLOSE 4864A01 L N L N AC 230 V N Y2 Y1 2AF N Y1 Y2 Q1 Q2 Y Q1 Q2 Controller contacts N Controller Y Actuator SP G System potentia...

Страница 8: ...кузнецк 3843 20 46 81 Новосибирск 383 227 86 73 Орел 4862 44 53 42 Оренбург 3532 37 68 04 Пенза 8412 22 31 16 Пермь 342 205 81 47 Ростов на Дону 863 308 18 15 Рязань 4912 46 61 64 Самара 846 206 03 16 Санкт Петербург 812 309 46 40 Саратов 845 249 38 78 Смоленск 4812 29 41 54 Сочи 862 225 72 31 Ставрополь 8652 20 65 13 Тверь 4822 63 31 35 Томск 3822 98 41 53 Тула 4872 74 02 29 Тюмень 3452 66 21 18 ...