background image

Document No. 997-1002 
Installation Instructions 
February 12, 2009

 

 

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as 
design improvements are introduced. Other product or company names mentioned herein may be the trademarks of their respective owners. 
© 2009 Siemens Building Technologies, Inc. 

 

Siemens Building Technologies, Inc.  

1000 Deerfield Parkway 
Buffalo Grove, IL  60089-4513 
U.S.A. 

 

Document No. 997-1002

Country of Origin: US

Page 8 of 8

 

16. Troubleshooting Guide 

 

 

Controller is powered but does not turn on 

Fuse has blown 

Check the fuse integrity. If the fuse has blown, perform the following: 

1.  Turn off power from the controller. 
2.  Remove the front plate of the controller. The fuse is located close to the power terminals. 
3.  Replace the fuse with a 2A fast-acting high-breaking capacity fuse (1500A @ 250VAC). Dimensions: 5 

x 20mm. 

4.  Reattach the front plate to the controller. 

Controller cannot communicate on an FTT network 

Absent or incorrect supply voltage 

1.  Check power supply voltage between the 85-265VAC and NEUTRAL pins and ensure that it is within 

acceptable limits. 

2.  Check for a  tripped fuse or circuit breaker. 

Network not wired properly 

Double check that the wire connections are correct. 

Absent or incorrect network termination 

Check the network termination(s). 

Incorrect APB file has been downloaded 

Use the memory erase jumper to reset the Neuron chip's memory. 

Service pin not working 

Use the memory erase jumper to reset the Neuron chip's memory. 

Controller communicates well over a short network, but does not communicate on large network

 

Network length 

Check that the total wire length does not exceed the specifications of the 

Junction Box and Wiring 

Guideline for Twisted Pair LonWorks Networks

Wire type 

Check that the wire type agrees with the specification of the 

Junction Box and Wiring Guideline for Twisted 

Pair LonWorks Networks

Network wiring problem 

Double check that the wire connections are correct. 

Absent or incorrect network termination 

Check the termination(s). Incorrect or broken termination(s) will make the communication integrity 
dependent upon a controller’s position on the network. 

Extra capacitance 

Make sure that no extra capacitance is being connected to the network other than the standard FTT circuit 
and a maximum of a 3 meter stub (in bus topology). 

Number of controllers on network 
segment exceeded 

The number of controllers on a channel should never exceed 64. Use a router or a repeater in accordance 
to the 

Junction Box and Wiring Guideline for Twisted Pair LonWorks Networks.

 

Network traffic 

Query node statistic to check errors. 
Use a LON protocol analyzer to check network traffic. 

Hardware input is not reading the correct value

 

Input wiring problem 

Check that the wiring is correct according to this document and according to the peripheral device’s 
manufacturer. 

Open circuit or short circuit 

Use a voltmeter, check the voltage on the input terminal. Short circuit (0V) and open circuit (5V). 

Configuration problem 

Use the controller configuration plug-in to check the configuration of the input. Refer to the controller’s user 
guide for more information. 

Hardware output is not operating correctly 

Output wiring problem 

Check that the wiring is correct according to this manual and according to the peripheral device’s 
manufacturer. 

Configuration problem 

Use the controller configuration plug-in to check the configuration of the output. Refer to the controller’s 
user guide for more information. 

Controller resets periodically 

Short circuit between 24VAC OUT and 
COM  

Make sure that the 24VAC OUT is not connected to the COM. 

Service LED  (Orange Color) 

Off 

The controller is in normal operation or not powered (if the controller is powered and the LED is off, pressing 
the Service Pin will light up the LED). 

On 

The controller is application-less.  
Appropriate action: Reload the application file (.apb).  

Slow Blink  
(1 sec. On, 1 sec. Off) 

The controller is unconfigured. 
Appropriate action: Commission the controller. 

Fast Blink  
(0.3 sec. On, 1 sec. Off) 

Watchdog time out. Application corrupted.  
Appropriate action: Use the memory erase jumper to reset the Neuron chip's memory, and then load the 
proper APB into the controller using a network management tool (e.g. LMT). 

Содержание SLX-ASC-PFCU

Страница 1: ...illers and boilers Moreover they are suitable for any lighting control and power measurement applications All of the controllers are based on the LONWORKS technology for peer to peer communication between controllers and are LONMARK certified Unless otherwise indicated the term PFCU is used in this document to represent both the SLX ASC PFCU and SLX ASC PFCU A models Likewise PTU represents both t...

Страница 2: ...electrical shock or burn Warning Symbol Significant information required Refer to Hardware Installation Guide Double Insulation Symbol These controllers are built with double insulation 4 General Wiring Recommendations Due to HIGH VOLTAGE direct contact will cause electrical shock or burn Turn off power before any kind of servicing It is recommended to use a 2 line main power disconnect to be loca...

Страница 3: ...h less than 75 23m either a shielded or unshielded 18AWG wire may be used For a wire length between 75 and 200 23 to 61m a shielded 18AWG wire is recommended The wire should be shielded on the controller side and the shield length should be kept as short as possible Wiring Digital Inputs This input configuration is used to monitor digital dry contacts as well as pulsed contacts PTU controllers onl...

Страница 4: ... to the installation guide of the equipment manufacturer Wiring Relay Contact Outputs Three 3 relay contact outputs DO1 DO3 can switch 3A inductive resistive for fan speed control up to 277VAC and one 1 relay contact output DO4 can switch 3A inductive and 10A resistive for heater control up to 277VAC Relay contact output cables must remain between 18 and 14AWG Select the proper gauge according to ...

Страница 5: ... 10VDC Universal Output Analog Actuator 11 Communications Wiring The recommended cable type for LON communications is 22AWG 0 65 mm twisted pair unshielded The LON communication wire is polarity insensitive and can be laid out in a bus star loop or free topology For loop topology polarity is important and special care must be taken when connecting the LON network to avoid a short circuit It is rec...

Страница 6: ... jumper 6 Reconnect the power The service LED will blink twice and become solid indicating that the controller is application less The proper APB using the Commission or Load option in LNS e g SLX Series LMT can now be loaded into the controller 13 Maintenance Due to HIGH VOLTAGE direct contact will cause electrical shock or burn Turn off power before any kind of servicing The PFCU and PTU control...

Страница 7: ...Page 7 of 8 15 Typical Fan Coil Application Wiring Diagram 4A Fast acting high breaking 5 x 20mm Fuse PART 216 004XP Littelfuse Fuse holder PART 3004100 Phoenix Contact 15A Fast acting high breaking 6 x 32mm Fuse PART 314015P Littelfuse Fuse holder PART 3004171 Phoenix Contact ...

Страница 8: ...etwork termination Check the termination s Incorrect or broken termination s will make the communication integrity dependent upon a controller s position on the network Extra capacitance Make sure that no extra capacitance is being connected to the network other than the standard FTT circuit and a maximum of a 3 meter stub in bus topology Number of controllers on network segment exceeded The numbe...

Отзывы: