background image

Document No. 997-1002 

Installation Instructions 

February 12, 2009 

 

SLX Series

 

Page 3 of 8

 

3. Remove the back plate and drill holes.  
4. Finally, clean the perforated surface and fasten the 

controller using the appropriate screw types. 

 

6.  Controller Dimensions  

 

 

 

Figure 3: PFCU and PTU Dimensions. 

 

7. Power 

Wiring 

Voltage:  

85-265VAC; 50-60Hz 

Max. Consumption: 33VA (SLX-ASC-PFCU-A and SLX-P-PTU-
A) 
  

20VA (SLX-ASC-PFCU and SLX-P-PTU)

 

The controller is internally fuse-protected. 

 

Figure 4: Power Wiring. 

 

The power wires must be at least 18AWG 
(1.024mm). 

 

8. Input 

Wiring 

Each controller has physical connections for six (6) inputs that 
are software configurable from within the controller's LNS

®

 

plug-in. Each input can be configured for digital, resistive, 
current or voltage signals. Input types must be configured 
properly in the software plug-in to ensure proper input 
readings. 

 

Before connecting any input equipment to the 
controller, refer to the installation guide of the 
equipment manufacturer. 

 

 

 

For a wire length less than 75’ (23m), either a 
shielded or unshielded 18AWG wire may be 
used. 

 

For a wire length between 75’ and 200’ (23 to 
61m), a shielded 18AWG wire is recommended. 

 

The wire should be shielded on the controller 
side and the shield length should be kept as 
short as possible. 

 

Wiring Digital Inputs 

This input configuration is used to monitor digital dry 
contacts, as well as pulsed contacts (PTU controllers only). 

 

Figure 5: Digital Dry Contact (NO and NC). 

 

Wiring Resistive Inputs 

This input configuration is used to monitor 100

 and 1000

 

RTDs, 10k

 type II and III thermistors, as well as 10k

 and 

100k

 (PTU controllers only) potentiometers. 

 

Figure 6: RTD /Thermistor Input. 

 

 

Figure 7: 10k

 Potentiometer Input. 

 

 

When using a 100

 input, the wire length should be 

kept short so as to avoid a possible temperature 
offset. For example, an 18AWG wire, 25’ (7.6m) in 
length can create an offset of 2°F (1.1°C). 

 
Wiring Current Inputs 

Current inputs have a range of 4 to 20mA. Connect the 
current input according to the following figure if a 2-wire, 4-
20mA transducer is being used. 

 

For safety reasons it is recommended to install the 
controller inside the fan coil unit box. Refer to 
national and local electrical codes. 

Содержание SLX-ASC-PFCU

Страница 1: ...illers and boilers Moreover they are suitable for any lighting control and power measurement applications All of the controllers are based on the LONWORKS technology for peer to peer communication between controllers and are LONMARK certified Unless otherwise indicated the term PFCU is used in this document to represent both the SLX ASC PFCU and SLX ASC PFCU A models Likewise PTU represents both t...

Страница 2: ...electrical shock or burn Warning Symbol Significant information required Refer to Hardware Installation Guide Double Insulation Symbol These controllers are built with double insulation 4 General Wiring Recommendations Due to HIGH VOLTAGE direct contact will cause electrical shock or burn Turn off power before any kind of servicing It is recommended to use a 2 line main power disconnect to be loca...

Страница 3: ...h less than 75 23m either a shielded or unshielded 18AWG wire may be used For a wire length between 75 and 200 23 to 61m a shielded 18AWG wire is recommended The wire should be shielded on the controller side and the shield length should be kept as short as possible Wiring Digital Inputs This input configuration is used to monitor digital dry contacts as well as pulsed contacts PTU controllers onl...

Страница 4: ... to the installation guide of the equipment manufacturer Wiring Relay Contact Outputs Three 3 relay contact outputs DO1 DO3 can switch 3A inductive resistive for fan speed control up to 277VAC and one 1 relay contact output DO4 can switch 3A inductive and 10A resistive for heater control up to 277VAC Relay contact output cables must remain between 18 and 14AWG Select the proper gauge according to ...

Страница 5: ... 10VDC Universal Output Analog Actuator 11 Communications Wiring The recommended cable type for LON communications is 22AWG 0 65 mm twisted pair unshielded The LON communication wire is polarity insensitive and can be laid out in a bus star loop or free topology For loop topology polarity is important and special care must be taken when connecting the LON network to avoid a short circuit It is rec...

Страница 6: ... jumper 6 Reconnect the power The service LED will blink twice and become solid indicating that the controller is application less The proper APB using the Commission or Load option in LNS e g SLX Series LMT can now be loaded into the controller 13 Maintenance Due to HIGH VOLTAGE direct contact will cause electrical shock or burn Turn off power before any kind of servicing The PFCU and PTU control...

Страница 7: ...Page 7 of 8 15 Typical Fan Coil Application Wiring Diagram 4A Fast acting high breaking 5 x 20mm Fuse PART 216 004XP Littelfuse Fuse holder PART 3004100 Phoenix Contact 15A Fast acting high breaking 6 x 32mm Fuse PART 314015P Littelfuse Fuse holder PART 3004171 Phoenix Contact ...

Страница 8: ...etwork termination Check the termination s Incorrect or broken termination s will make the communication integrity dependent upon a controller s position on the network Extra capacitance Make sure that no extra capacitance is being connected to the network other than the standard FTT circuit and a maximum of a 3 meter stub in bus topology Number of controllers on network segment exceeded The numbe...

Отзывы: