Name
Type
Address Default
Range of Values / Explanation
Reference
Value range 200h – 23Fh
200h+ 0...1Fh Bit-No. NAWI status bit - going
200h+ 20h...3Fh Bit-No. AWI status bit - going
S7 - FB Life bit
monitoring time
TIME
DBB024
0
0 = S7- Life bit monitor switched off
1 to n = Monitor time [msec]
Analog output
0
Weight for zero point
(0 or 4 mA)
REAL
DBB028
0
Value output with the 0 or 4 mA
Reference for end value
(20 mA)
REAL
DBB032
0
Value output with the 20 mA.
Replacement value for
the analog output at OD
REAL
DBB036
0
Replacement value which is output with the
active OD signal if defined.
Source for the analog
output
BYTE
DBB040
0
0 = Control signals-SIMATIC
1 = Ext. default value with DR 17
2 = Gross
3 = Net
Coarse/fine default values
Other definitions not permitted.
Current range for the
analog output
BYTE
DBB041
0
Bit 0 :
0: 0 .. 20mA
1: 4 .. 20mA
Bit 1 – 7 unused
RS232
0
RS232-printer baud rate
BYTE
DBB042
3
0 = 1200 Bit/sec.
1 = 2400 Bit/sec.
2 = 4800 Bit/sec.
3 = 9600 Bit/sec.
Other definitions not permitted.
RS232-XON/XOFF for
printer
RS232-RTS/CTS for
printer
BYTE
DBB043
1
Bit 0 :
0: XON/XOFF transmission control OFF
1: XON/XOFF transmission control ON
Bit 1 :
0: CTS/RTS transmission control OFF
1: CTS/RTS transmission control ON
Bit 2 : Reserved, must always be 0
Bit 3 – 7 unused
RS485
0
Log selection
BYTE
DBB044
0
0:
No device
1:
SIEBERT Display S11
2:
Reserved
3:
SIEBERT – Display S102
Decimal place for the
remote display
BYTE
DBB045
0
0 to 4
Other definitions not permitted.
RS485-Baudrate
BYTE
DBB046
3
0 = 1200 Bit/sec.
1 = 2400 Bit/sec.
2 = 4800 Bit/sec.
3 = 9600 Bit/sec.
4 = 19200 Bit/s
5 = 38400 Bit/s
Other definitions not permitted.