SITRANS RD300 – OPERATING INSTRUCTIONS
Page 31
Programming the Meter (
prog
)
It is
very important
to read the following information, before proceeding
to program the meter:
The meter is factory calibrated prior to shipment to read in
milliamps and volts depending on the input selection. The
calibration equipment is certified to NIST standards.
Use the
Scale
menu to scale the process input (e.g. 4-20 mA). A
calibrated signal source is not needed to scale the meter.
Use the
Calibrate
menu to apply a signal from a calibrator or a
flowmeter.
The RD300 is a single input meter with dual-scale capability.
The
Program
menu contains the
Scale
and the
Calibrate
menus.
Note: The
Scale
and
Calibrate
functions are exclusive of each other.
The meter uses the last function programmed. Only one of these
methods can be employed at a time. The Scale and Calibrate functions
can use up to 32 points (default is 2). The number of points should be set
in the Advanced menu under the Multi-Point Linearization
(Linear)
menu
selection prior to scaling and calibration of the meter, see page 80 for
details.
If the dual-scale level feature is selected in the
Setup
menu, the
Scale 1
and
Scale 2
menus are enabled for PV1 & PV2 respectively.
The process input may be calibrated or scaled to any display value
within the range of the meter.
Program Menu for Single Scale Process
Program Menu for Dual-Scale Level Applications
Additional parameters, not needed for most applications, are
programmed in the
Advanced
Features
menu; see
Advanced Features
Menu
, page 74.