SITRANS P DS III/P410 (7MF4.33.. 7MF4.34.. 7MF4.35..)
40
A5E03434626-04, 05/2015
Absolute pressure input (from the differential pressure series)
5.3 … 100 bar a
0.5 ... 10 MPa a
76.9 … 1450 psi a
160 bar a
16 MPa a
2320 psi a
Lower measuring limit
•
Measuring cell with silicone oil filling
0 mbar a /kPa a /psi a
•
Measuring cell with inert liquid
for process temperature -20°C <
ϑ
≤
60°C (-4°F <
ϑ
≤
+140°F)
30 mbar a /3 kPa a /0.44 psi a
for process temperature 60°C <
ϑ
≤
100°C (max. 85°C for measuring
cell 30 bar) (140°F <
ϑ
≤
212°F
(max. 185°F for measuring cell
435 psi))
30 mbar a + 20 mbar
a •
(
ϑ
- 60 °C)/°C
3 kPa a + 2 kPa
a •
(
ϑ
- 60 °C)/°C
0.44 psi a + 0.29 psi
a •
(
ϑ
- 108 °F)/°F
Upper measuring limit
100 % of max. span (for oxygen measurement: max.
100 bar/10 MPa/1450 psi and 60 °C ambient temperature/process
temperature)
Start of scale value
Between the measuring limits (fully adjustable)
1)
Order the nominal measuring range with the order option Y01 for PROFIBUS PA or FOUNDATION Fieldbus.
Differential pressure and flow rate input
Measured variable
Differential pressure and flow rate
Span (continuously adjustable) or
measuring range and max. operating
pressure (in accordance with 97/23/EC
Pressure Equipment Directive)
Span
1)
Maximum operating pressure MAWP
(PS)
1 ... 20 mbar
0.1 ... 2 kPa
0.4015 … 8.031 inH
2
O
32 bar
3.2 MPa
464 psi
1 ... 60 mbar
0.1 ... 6 kPa
0.4015 … 24.09 inH
2
O
160 bar
16 MPa
2320 psi
2.5 … 250 mbar
0.2 ... 25 kPa
1.004 … 100.4 inH
2
O
6 … 600 mbar
0.6 ... 60 kPa
2.409 … 240.9 inH
2
O
16 … 1600 mbar
1.6 ... 160 kPa
6.424 … 642.4 inH
2
O
50 … 5000 mbar
5 ... 500 kPa
20.08 … 2008 inH
2
O
0.3 … 30 bar
0.03 ... 3 MPa
4.35 … 435 psi
2.5 … 250 mbar
0.25 ... 25 kPa
1.004 … 100.4 inH
2
O
420 bar
42 MPa
6091 psi