
Connecting
5.1 SITRANS FUE380 and FUS380
5.1
SITRANS FUE380 and FUS380
Power for pulse output from SITRANS FUE380 and FUE380 is automatically supplied via
energy calculator terminals 10 and 11:
FUE380/FUS380 terminal
FUE950 terminal
56
10
57
11
56
57
FUE380/FUS380
FUE950
Note
Use shielded cable. Connect shield to grounding at flowmeter (e. g. the clamp of FUE380).
For connection of flowmeter, see flowmeter operating instructions.
5.2
SITRANS F M MAG 5000/6000
When MAG 5000/6000 and SITRANS FUE950 are connected as a heat meter, 2 resistors
are required to obtain a correct transmission of pulses.
The 2 resistors must be mounted between terminals 57 and 58 in the MAG terminal socket.
Resistors are part of neither delivery nor accessories list.
MAG 5000/6000 terminal
FUE950 terminal
57
10
58
11
SITRANS FUE950
24
Operating Instructions, 01/2010, SFIDK.PS.022.F4.02
Содержание SITRANS FUE950
Страница 1: ...SITRANS F Ultrasonic Flowmeters SITRANS FUE950 Energy Calculator Operating Instructions Jan 2010 ...
Страница 2: ......
Страница 12: ...Safety notes 2 3 General requirements SITRANS FUE950 10 Operating Instructions 01 2010 SFIDK PS 022 F4 02 ...
Страница 50: ...Operation hardware 6 4 Function test SITRANS FUE950 48 Operating Instructions 01 2010 SFIDK PS 022 F4 02 ...
Страница 70: ...Appendix A 2 Certificates SITRANS FUE950 68 Operating Instructions 01 2010 SFIDK PS 022 F4 02 ...