Installing/Mounting
4.4 Installation of device
Panel mounting
Mounting hole must be 94 x 128 mm (3.70 x 5.04 in). Device is fixed using M3 x 10 mm self-
tapping screws.
(
)
(
)
94
(3
7)
70
(70.2)
Figure 4-2
Panel mounting of device
Installing temperature sensors
Note
Important!
Handle temperature sensors with care.
Temperature sensors are matched paired sets and must never be separated.
Temperature sensor cable length must not be altered as it affects the meter accuracy.
Sensor pockets must be the same for cold pipe and hot pipe, and also mounted in the same
way.
Observe the right temperature sensor installation in application. Sensor cables are provided
with colored type labels: Red for warm line temperature sensor and blue for cold line
temperature sensor.
Install temperature sensors in pipe lines using pockets (if ordered in separate bag) by
inserting them in the two pockets installed in the forward and return pipes.
Fix sensors in pockets using the screws and make a user sealing for each sensor at the
pockets
Figure 4-3
Sealing of temperature sensor at pocket
SITRANS FUE950
18
Operating Instructions, 01/2010, SFIDK.PS.022.F4.02
Содержание SITRANS FUE950
Страница 1: ...SITRANS F Ultrasonic Flowmeters SITRANS FUE950 Energy Calculator Operating Instructions Jan 2010 ...
Страница 2: ......
Страница 12: ...Safety notes 2 3 General requirements SITRANS FUE950 10 Operating Instructions 01 2010 SFIDK PS 022 F4 02 ...
Страница 50: ...Operation hardware 6 4 Function test SITRANS FUE950 48 Operating Instructions 01 2010 SFIDK PS 022 F4 02 ...
Страница 70: ...Appendix A 2 Certificates SITRANS FUE950 68 Operating Instructions 01 2010 SFIDK PS 022 F4 02 ...