Appendix A
A.1 Modbus, EIP, HART & N2 Profile Mappings
F US Clamp-on Communications Protocol Manual
Hardware Installation Manual, 11/2015, A5E34981613-AC
89
C2 Inst.Flow
Rate
30111 4
Real
Analog_In 18 Float
129 7-07h ADF
(Float)
13
1
C2 Avg Flow
Rate
30123 4
Real
Analog_In 19 Float
129 2-02
hT
ADF
(Float)
14
1
C2 Flow Rate
Units
30521 8
String String_In 52 UINT16 131 2-02h BD(Byte)
105 8
C2 Total
30147 4
Real
Analog_In 20 Float
129 35-23h
Q
ADF
(Float)
15
1
C2 Total Units
30561 8
String String_In 56 UINT16 131 35-23h BD(Byte)
113 8
C2 Status
/Alarms: Spacing
10041 1 Bit
Coil
Binary_In 1
UINT16
n/a
DI(Dig In)
10
1
C2 Status
/Alarms: Empty
10042 1 Bit
Coil
Binary_In 1
UINT16
n/a
DI(Dig In)
12
1
C2 Status
/Alarms: Rate
10043 1 Bit
Coil
Binary_In 1
UINT16
n/a
DI(Dig In)
13
1
C2 Status
/Alarms: Fault
10044 1 Bit
Coil
Binary_In 1
UINT16
n/a
DI(Dig In)
14
1
C2 Status
/Alarms: Aeration
10045 1 Bit
Coil
Binary_In 1
UINT16
n/a
DI(Dig In)
15
1
C2 Status
/Alarms: Memory
10046 1 Bit
Coil
Binary_In 1
UINT16
n/a
DI(Dig In)
16
1
C2 Status
/Alarms: Makeup
10047 1 Bit
Coil
Binary_In 1
UINT16
n/a
DI(Dig In)
17
1
C2 Status
/Alarms: Interface
10048 1 Bit
Coil
Binary_In 1
UINT16
n/a
DI(Dig In)
18
1
C2 Status
/Alarms: Zeroma-
tic
10050 1 Bit
Coil
Binary_In 1
UINT16
n/a
DI(Dig In)
11
1
Temperature 2
30295 4
Real
Analog_In 21 Float
n/a
ADF
(Float)
16
1
Temp 2 Units
30761 8
String String_In 60 UINT16
n/a
BD(Byte)
121 8
Aux Input 3
30289 4
Real
Analog_In 22 Float
n/a
ADF
(Float)
17
1
Aux 3 Type
30821 8
String String_In 64 UINT16
n/a
BD(Byte)
129 8
Aux Input 4
30291 4
Real
Analog_In 23 Float
n/a
ADF
(Float)
18
1
Aux 4 Type
30825 8
String String_In 68 UINT16
n/a
BD(Byte)
137 8
C2 Percent
Deviation
30191 4
Real
Analog_In 24 Float
n/a
ADF
(Float)
19
1
C2 Deviation
Units
30649 8
String String_In 72 UINT16
n/a
BD(Byte)
145 8