Appendix A
A.1 Modbus, EIP, HART & N2 Profile Mappings
F US Clamp-on Communications Protocol Manual
Hardware Installation Manual, 11/2015, A5E34981613-AC
169
Status: Zeromatic
Path 1
10030 1 Bit
Coil
Binary_In
0
UINT16
n/a
DI(Dig In)
2
1
Status: Spacing
Path 2
10041 1 Bit
Coil
Binary_In
1
UINT16
n/a
DI(Dig In)
11 1
Status: Empty
Path 2
10042 1 Bit
Coil
Binary_In
1
UINT16
n/a
DI(Dig In)
13 1
Status: Rate
Path 2
10043 1 Bit
Coil
Binary_In
1
UINT16
n/a
DI(Dig In)
14 1
Status: Fault
Path 2
10044 1 Bit
Coil
Binary_In
1
UINT16
n/a
DI(Dig In)
15 1
Status: Aeration
Path 2
10045 1 Bit
Coil
Binary_In
1
UINT16
n/a
DI(Dig In)
16 1
Status: Memory
Path 2
10046 1 Bit
Coil
Binary_In
1
UINT16
n/a
DI(Dig In)
17 1
Status: Makeup
Path 2
10047 1 Bit
Coil
Binary_In
1
UINT16
n/a
DI(Dig In)
18 1
Status: Interface
Path 2
10048 1 Bit
Coil
Binary_In
1
UINT16
n/a
DI(Dig In)
19 1
Status: Pig
Path 2
10049 1 Bit
Coil
Binary_In
1
UINT16
n/a
DI(Dig In)
20 1
Status: Zeromatic
Path 2
10050 1 Bit
Coil
Binary_In
1
UINT16
n/a
DI(Dig In)
12 1
Status: Spacing
Path 3
10061 1 Bit
Coil
Binary_In
2
UINT16
n/a
DI(Dig In)
21 1
Status: Empty
Path 3
10062 1 Bit
Coil
Binary_In
2
UINT16
n/a
DI(Dig In)
23 1
Status: Rate
Path 3
10063 1 Bit
Coil
Binary_In
2
UINT16
n/a
DI(Dig In)
24 1
Status: Fault
Path 3
10064 1 Bit
Coil
Binary_In
2
UINT16
n/a
DI(Dig In)
25 1
Status: Aeration
Path 3
10065 1 Bit
Coil
Binary_In
2
UINT16
n/a
DI(Dig In)
26 1
Status: Memory
Path 3
10066 1 Bit
Coil
Binary_In
2
UINT16
n/a
DI(Dig In)
27 1
Status: Makeup
Path 3
10067 1 Bit
Coil
Binary_In
2
UINT16
n/a
DI(Dig In)
28 1
Status: Interface
Path 3
10068 1 Bit
Coil
Binary_In
2
UINT16
n/a
DI(Dig In)
29 1
Status: Pig
Path 3
10069 1 Bit
Coil
Binary_In
2
UINT16
n/a
DI(Dig In)
30 1
Status: Zeromatic
Path 3
10070 1 Bit
Coil
Binary_In
2
UINT16
n/a
DI(Dig In)
22 1
Status: Spacing
Path 4
10081 1 Bit
Coil
Binary_In
3
UINT16
n/a
DI(Dig In)
31 1
Status: Empty
Path 4
10082 1 Bit
Coil
Binary_In
3
UINT16
n/a
DI(Dig In)
33 1
Status: Rate
Path 4
10083 1 Bit
Coil
Binary_In
3
UINT16
n/a
DI(Dig In)
34 1
Status: Fault
Path 4
10084 1 Bit
Coil
Binary_In
3
UINT16
n/a
DI(Dig In)
35 1
Status: Aeration
Path 4
10085 1 Bit
Coil
Binary_In
3
UINT16
n/a
DI(Dig In)
36 1