Installing/Mounting
2.3 Flowmeter Setup
F US Clamp-on Communications Protocol Manual
18
Hardware Installation Manual, 11/2015, A5E34981613-AC
choices. Use the <Right> arrow key to access the choices. Using the <UP/DN> arrow
keys, select the item desired as defined below. Pressing the <ENTER> key will select that
choice.
●
Logger Mode: Set to RS-232 Output
●
Logger Data ON: Select All Items (Note: If any FUH1010 system, DO NOT select
[Sonilocator] in the Logger Data drop down menu.)
●
Log Interval Set: Set to 5 secs
●
Logger Events: Set to NONE
Press the <Right> arrow to access. Highlight each Logger item using the <UP/DN> arrow
keys, and then press the <ENTER> key to set EVERY choice on. Each item will have [+]
sign to left of item when selected.
Use the <Left> arrow key to back out of the nested menu to return to the top menu. Use of
the <Left> arrow key intermediately saves the configuration information permanently. You
also must then Re-Save the site.
Channel Setup
For each channel set the Logger to [On Demand.]
1.
Set all Data elements: ON (denoted by +)
2.
Set [Events]: Off
3.
Set [display/Memory Datalogger: Off
4.
Enable all Channels
Note
If ALL channels are not [Enabled], the Modbus card will NOT provide valid data.
Note
For all 1010 flowmeters the site names must be duplicated on the Communications Module
Card itself.
Please view the "Web Configuration Utility" at the end of this procedure and refer and follow
the instructions concerning "site_idx"